Chapter 9
Review the 1734-4IOL IO-Link AOP
Data Mapping Configuration
In this section, the operator is able to configure the process data to be used. The
process data consists of 4 bytes of data. The following process data maps are
offered in the 871FM sensor:
• Data Map 0 (Default): Triggered, Margin, Proximity, Gain, Signal
• Data Map 1: Triggered, Margin, Proximity, Gain, Contrast, Temp
• Data Map 2: Triggered, Margin, Proximity, Gain, Count
• Data Map 3: Triggered, Margin, Proximity, Gain, Duration
Attribute Description
Triggered
Displays the status of the sensor output. This process data element is a bit that indicates when the
target has been detected or not.
Margin
Displays the status of the sensor margin low alarm. This process data element is a bit that indicates to
the operator if the sensor signal is marginal or unstable.
Proximity
Displays the status of the proximity alarm. This process data element is a bit that indicates if there is
an object close to the threshold (below 1.0X) when the output is OFF.
Gain
Displays the excess gain above the sensor threshold to confirm reliability of target detection.
Signal
Provides the raw measurement value of the amount of light reflected from the target.
Contrast
Displays the difference between the light signal levels that the sensor read the last time that the
output was ON versus the last time the output was OFF.
Temp
Displays the current internal temperature of the sensor. This process data element provides the
internal temperature value and can increase or decrease depending on the influence of the ambient
temperature on the internal sensor temperature. This element does not provide a direct and exact
temperature measurement of the ambient temperature in the application.
Count
Displays the sensor counter value when enabled. This process data element can count up to 65535
and can be reset via Explicit Messaging to the appropriate index. See
for additional information about index.
Duration
Displays the amount of time that the sensor output has been OFF (Duration Not Triggered) and ON
(Duration Triggered).
Содержание Allen-Bradley 871FM-M10BA30-x
Страница 6: ...6 Rockwell Automation Publication 871FM UM002A EN P April 2017 Table of Contents Notes...
Страница 8: ...8 Rockwell Automation Publication 871FM UM002A EN P April 2017 Preface Notes...
Страница 12: ...12 Rockwell Automation Publication 871FM UM002A EN P April 2017 Chapter 1 Product Overview Notes...
Страница 28: ...28 Rockwell Automation Publication 871FM UM002A EN P April 2017 Chapter 5 Create a Project Notes...
Страница 46: ...46 Rockwell Automation Publication 871FM UM002A EN P April 2017 Chapter 8 Register the 871FM IODD Notes...
Страница 66: ...66 Rockwell Automation Publication 871FM UM002A EN P April 2017 Chapter 11 Troubleshooting Notes...
Страница 84: ...84 Rockwell Automation Publication 871FM UM002A EN P April 2017 Appendix D Explicit Messaging Examples Notes...
Страница 88: ...88 Rockwell Automation Publication 871FM UM002A EN P April 2017 Index Notes...
Страница 89: ......