26
Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Chapter 2
Planning the Kinetix 6000 Drive System Installation
Circuit Breaker/Fuse Selection
The Kinetix 6000 drives use internal solid-state motor short-circuit protection
and, when protected by suitable branch circuit protection, are rated for use on a
circuit capable of delivering up to 200,000 A. Fuses or circuit breakers, with
adequate withstand and interrupt ratings, as defined in NEC or applicable local
codes, are permitted.
The 2094-AL09 and 2094-BL02 LIM modules contain supplementary
protection devices and, when protected by suitable branch circuit protection, are
rated for use on a circuit capable of delivering up to 5000 A. When these modules
are used, protection on the line side of the LIM module is required. Fuses must be
class J or CC only.
The 2094-AL
xx
S, 2094-BL
xx
S, and 2094-XL75S-C
x
LIM modules contain
branch circuit rated devices suitable for use on a circuit capable of delivering up
to 65,000 A (460V) or 100,000 A (230V).
Refer to the Line Interface Module Installation Instructions, publication
, for power specifications and more information on using the LIM
module.
The Bulletin 140M and 140U products are another acceptable means of
protection. As with fuses and circuit breakers, you must make sure that the
selected components are properly coordinated and meet applicable codes
including any requirements for branch circuit protection. When applying the
140M/140U product, evaluation of the short circuit available current is critical
and must be kept below the short circuit current rating of the 140M/140U
product.
In most cases, class CC, J, L, and R fuses selected to match the drive input current
rating will meet the NEC requirements or applicable local codes, and provide the
full drive capabilities. Dual element, time delay (slow-acting) fuses should be
used to avoid nuisance trips during the inrush current of power initialization.
Refer to Circuit Breaker/Fuse Specifications on
for recommended
circuit breakers and fuses.
Refer to Power Specifications on
for input current and inrush current
specifications for your IAM module.
Содержание Allen-Bradley 2094-BC01-M01-S
Страница 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Страница 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Страница 126: ...126 Rockwell Automation Publication 2094 UM001D EN P May 2010 Chapter 5 Connecting the Kinetix 6000 Drive System Notes...
Страница 228: ...228 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix B Interconnect Diagrams Notes...
Страница 270: ...270 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix F RBM Module Interconnect Diagrams Notes...
Страница 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Страница 279: ......