Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
187
Specifications and Dimensions
Appendix A
Circuit Breaker/Fuse Specifications
While circuit breakers offer some convenience, there are limitations for their use.
Circuit breakers do not handle high current inrush as well as fuses.
Circuit breakers not rated for branch circuit protection under UL 489, for
example Bulletin 1492 devices, require upstream protection.
Use class CC, J, L, or R fuses, with current rating as indicated in the table below.
These fuse examples and Allen-Bradley circuit breakers are recommended for use
with 2094-
x
C
xx
-M
xx
-
x
IAM modules when the LIM module is not used.
Refer to IAM Module (without LIM module), on
, for the wiring
diagram.
IMPORTANT
Line Interface Modules (catalog numbers 2094-AL
xx
S, 2094-BL
xx
S, and
2094-XL75S-C
x
) provide branch circuit protection to the IAM module.
Follow all applicable NEC and local codes.
IAM/AM Module
V AC Input Power
Control Input Power
DC Common Bus Fuse
Bussmann
Fuse
Allen-Bradley Circuit Breaker
Bussmann
Fuse
Allen-Bradley
Circuit Breaker
Bussmann
Fuse
Ferraz
Shawmut Fuse
Disconnect
Magnetic
Contactor
2094-AC05-MP5-
x
KTK-R-20 (20 A) 1492-SP3D300
140M-F8E-C16
FNQ-R-10 (10 A)
1492-SP2D060
N/A
A50P20-1
2094-AC05-M01-
x
2094-AC09-M02-
x
KTK-R-30 (30 A) 1492-SP3D400
140M-F8E-C20
FWH-35B
A50P35-4
2094-AC16-M03-
x
LPJ-45SP (45 A) N/A
140U-H6C3-C50
1492-SP2D200
FWH-60B
A50P60-4
2094-AC32-M05-
x
LPJ-80SP (80 A) N/A
140U-H6C3-C90
FWH-125B
A50P125-4
2094-BC01-MP5-
x
KTK-R-20 (20 A) 1492-SP3D300
140M-F8E-C32
FNQ-R-10 (10 A)
1492-SP2D060
N/A
A100P20-1
2094-BC01-M01-
x
2094-BC02-M02-
x
KTK-R-30 (30 A) 1492-SP3D400
140M-F8E-C45
FWJ-40A
A100P40-1
2094-BC04-M03-
x
LPJ-45SP (45 A)
N/A
140U-H6C3-C50
1492-SP2D060
FWJ-70A
A100P70-1
2094-BC07-M05-
x
LPJ-80SP (80 A)
140U-H6C3-C90
FWJ-125A
A100P125-1
ATTENTION:
Bulletin 1492, 140M, and 140U products should not be used
on the output of an AC drive as an isolating disconnect switch or motor
overload device. These devices are designed to operate on sine wave
voltage and the drive’s PWM waveform does not allow it to operate
properly. As a result, damage to the device will occur.
Содержание Allen-Bradley 2094-BC01-M01-S
Страница 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Страница 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Страница 126: ...126 Rockwell Automation Publication 2094 UM001D EN P May 2010 Chapter 5 Connecting the Kinetix 6000 Drive System Notes...
Страница 228: ...228 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix B Interconnect Diagrams Notes...
Страница 270: ...270 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix F RBM Module Interconnect Diagrams Notes...
Страница 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Страница 279: ......