![Rockwell Automation Allen-Bradley 1606-XLDF240F Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/rockwell-automation/allen-bradley-1606-xldf240f/allen-bradley-1606-xldf240f_reference-manual_1475677009.webp)
Rockwell Automation Publication 1606-RM124A-EN-P - September 2021
9
DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual
Hold-up Time
The input side of the DC/DC converter is equipped with a bulk capacitor that
keeps the output voltage alive for a certain time period when the input voltage
dips or is removed. The bulk capacitor can be discharged by loading the DC/DC
converter on the output side or through a load that is parallel to the input.
There is no protection in the DC/DC converter that helps prevent current from
flowing back to the input terminals. If prevention is needed, use an external
diode.
At no load, the hold-up time can be up to several seconds. During this time, the
green DC-OK lamp is also on.
Output current
Nom
6 A
At 48V and an ambient temperature below 45 °C (113 °F)
.
5 A
At 48V and 60 °C (140 °F) ambient temperature
.
3.8 A
At 48V and 70 °C (158 °F) ambient temperature
.
5.2 A
At 56V and an ambient temperature below 45 °C (113 °F)
.
4.3 A
At 56V and 60 °C (140 °F) ambient temperature
.
3.2 A
At 56V and 70 °C (158 °F) ambient temperature
.
Overload behavior
—
Continuous current
—
Overload/short-circuit current
Max
7 A
Continuous current, short-circuit impedance <90 m
Ω
.
Output capacitance
Typ
1750 µF
Included inside the power supply.
Back-feeding loads
Max
63V
The unit is resistant and does not show malfunctioning when a load feeds back
voltage to the power supply
.
It does not matter whether the power supply is on or off.
The absorbing energy can be calculated according to the built-in, large-sized output
capacitor.
Figure 6 - Output Voltage Versus Output Current at
48V DC Input Voltage, Typical
Figure 7 - Current Limitation Versus Input Voltage,
(46V Constant Voltage Load), Typical
Output Voltage (V)
0
4
5
6
8
16
24
56
32
40
48
8
3
1
2
0
7
Adjustment
Range
Output Current (A)
5.0
6.0
7.0
30
35
45
50
60
Input Voltage (V DC)
Output Current (A)
6.5
55
5.5
40
Attributes
Values
Notes
Hold-up Time
Typ
14 ms
At 48V DC input voltage, 48V, 2.5 A output; see
Min
11 ms
At 48V DC input voltage, 48V, 2.5 A output; see
Typ
7.7 ms
At 48V DC input voltage, 48V, 0.5 A output; see
.
Min
6.2 ms
At 48V DC input voltage, 48V, 5 A output; see
Figure 8 - Hold-up Time Versus Input Voltage
Figure 9 - Shutdown Test Setup
0
3
9
12
18
36
40
44
48
56
Input Voltage (V DC)
Hold-up Time (ms)
52
(a)
(b)
(c)
(d)
6
15
(a) 48V, 2.5A, typ.
(b) 48V, 2.5A, min.
(c) 48V, 5A, typ.
(d) 48V, 5A, min.
Load
DC
Source
+
-
Input
Output
+
-
+
-
S1
1606-XLDF240F