background image

12

Rockwell Automation Publication 1606-RM124A-EN-P - September 2021

DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual

Daisy Chaining of Outputs

Daisy chaining (jumping from one DC/DC-converter output to the next) is 
permitted, as long as the average output current through one terminal pin 
does not exceed 25 A. If the current is higher, use a separate distribution 
terminal block.

Lifetime Expectancy

The Lifetime expectancy that is shown in the table indicates the minimum 
operating hours (service life) and is determined by the lifetime expectancy of 
the built-in electrolytic capacitors. Lifetime expectancy is specified in 
operational hours and is calculated according to the capacitor’s manufacturer 
specification.

The manufacturer of the electrolytic capacitors only states a maximum life of 
up to 15 years (131,400 hr). Any number that exceeds this value is a calculated 
theoretical lifetime, which can be used to compare devices.

Mean Time Between Failure

Mean time between failure (MTBF) is calculated according to statistical device 
failures, and indicates reliability of a device. The MTBF value is a statistical 
representation of the likelihood of a unit to fail and does not necessarily 
represent the life of a product. An MTBF value of, for example, 1,000,000 hr 
means that statistically one unit fails every 100 hours if 10,000 units are 
installed in the field. However, it cannot be determined if the failed unit has 
been running for 50,000 hr or only for 100 hr.

For these types of units, the Mean Time to Failure (MTTF) value is the same as 
the MTBF value.

Figure 17 - Daisy Chaining of Outputs

Figure 18 - Using Distribution Terminals

Converter

DC/DC

 +

+

-

-

 +

+

-

-

Input

Converter

DC/DC

Input

Load

+

-

25 A, max

Output

Output

Distribution

Terminals

Converter

DC/DC

 +

+

-

-

 +

+

-

-

Input

Converter

DC/DC

Input

Load

+

-

Output

Output

Attributes

Input 48V DC Notes

Lifetime expectancy

160,000 hr

At 48V, 5 A, and 40 °C (104 °F)

307,000 hr

At 48V, 2.5 A, and 40 °C (104 °F)

112,000 hr

At 48V, 6 A, and 40 °C (104 °F)

453,000 hr

At 48V, 5 A, and 25 °C (77 °F)

868,000 hr

At 48V, 2.5 A, and 25 °C (77 °F)

318,000 hr

At 48V, 6 A, and 25 °C (77 °F)

Attributes

Input 48V DC Notes

MTBF SN 29500, IEC 61709

853 kHz

At 48V, 5 A, and 40 °C (104 °F)

1512 kHz

At 48V, 5 A, and 25 °C (77 °F)

MTBF MIL HDBK 217F

285 kHz

At 48V, 5 A, and 40 °C (104 °F); Ground Benign GB40

421 kHz

At 48V, 5 A, and 25 °C (77 °F); Ground Benign GB25

71 kHz

At 48V, 5 A, and 40 °C (104 °F); Ground Fixed GF40

97 kHz

At 48V, 5 A, and 25 °C (77 °F); Ground Fixed GF25

Содержание Allen-Bradley 1606-XLDF240F

Страница 1: ...DC DC Converter 48V 48V 5 A 240 W Catalog Number 1606 XLDF240F Reference Manual Original Instructions...

Страница 2: ...ell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission...

Страница 3: ...romagnetic Compatibility 13 Environment 14 Safety and Protection Features 15 Dielectric Strength 15 Approved Fulfilled or Tested Standards 16 Regulatory Product Compliance 16 Physical Dimensions and W...

Страница 4: ...4 Rockwell Automation Publication 1606 RM124A EN P September 2021 Table of Contents Notes...

Страница 5: ...DC output Efficiency up to 95 1 Width only 42 mm 1 65 in 20 output power reserves Full power between 25 60 C 13 140 F Soft start function Minimal inrush current surge Reverse input polarity protection...

Страница 6: ...x 4 88 x 4 61 in Without DIN rail Weight 500 g 1 1 lb Catalog Numbers Description 1606 XLDF240F DC DC converter 1606 XLC Wall or panel mount bracket see page 17 1606 XLA S44 Side mount bracket see pag...

Страница 7: ...led inside the device external capacitors on the input are allowed without any limitations External input protection The device is designed tested and approved for branch circuits up to 50 A without a...

Страница 8: ...his function increases the rise time of the output voltage by a small amount Output The output provides a SELV PELV rated voltage which is galvanically isolated from the input voltage and is designed...

Страница 9: ...t current Max 7 A Continuous current short circuit impedance 90 m Output capacitance Typ 1750 F Included inside the power supply Back feeding loads Max 63V The unit is resistant and does not show malf...

Страница 10: ...A 94 9 At 48V 6 A power boost Average efficiency Typ 94 6 25 at 1 25 A 25 at 2 5 A 25 at 3 75 A 25 at 5 A Power losses Typ 2 1 W At no output load 6 7 W At 48V 2 5 A 12 4 W At 48V 5 A 15 5 W At 48V 6...

Страница 11: ...inals screw terminals Dual terminals for the negative and positive pole Both poles are internally connected Positive output Negative return output 2 Output voltage potentiometer Open the flap to set t...

Страница 12: ...tical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product An MTBF value of for example 1 000 000 hr means that statistically one unit fails ever...

Страница 13: ...discharge 8 kV Criterion A Air discharge 15 kV Criterion A Electromagnetic RF field EN 61000 4 3 80 MHz 2 7 GHz 20V m Criterion A Fast transients Burst EN 61000 4 4 Input lines 4 kV Criterion A Outpu...

Страница 14: ...1 Shock and vibration are tested in combination with DIN rails according to EN 60715 with a height of 15 mm 0 59 in and a thickness of 1 3 mm 0 05 in These tests are performed with the DC DC converter...

Страница 15: ...input and PE measured with 500V DC Min 500 M At delivered condition between output and PE measured with 500V DC PE resistance Max 0 1 Resistance between PE terminal and the housing in the area of the...

Страница 16: ...he Council of June 1 2007 regarding the Registration Evaluation Authorization and Restriction of Chemicals REACH Ind Cont Eq Attributes Values and Descriptions Width 42 mm 1 65 in Height 124 mm 4 88 i...

Страница 17: ...ins the two brackets that are needed for one device Figure 22 Cat No 1606 XLC Wall Panel Mount Bracket Side Mount Bracket Cat No 1606 XLA S44 This bracket mounts the device sideways with or without us...

Страница 18: ...the perfect choice when the power supply has no DC OK function Two light emitting diode LEDs and two relay contacts signal when one of the two input voltages is not in range due to a non functioning...

Страница 19: ...discharged during such an event which causes a voltage dip on the output Figure 24 and Figure 25 show two typical voltage dips Output Circuit Breakers Standard miniature circuit breakers MCB s or UL 1...

Страница 20: ...DC must be installed with protection against touching Avoid return voltage for example from a decelerating motor or battery that is applied to the output terminals Keep a left right installation clea...

Страница 21: ...Redundancy Devices can be paralleled for 1 1 redundancy to gain higher system availability Redundant systems require a certain amount of extra power to support the load in case one device fails The si...

Страница 22: ...ide of the DC DC converter with a distance of 1 cm 0 39 in The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure Figure 26 1 1 Redundant Co...

Страница 23: ...28 Mounting Orientation A upright standard Figure 29 Mounting Orientation B upside down Figure 30 Mounting Orientation C table top Figure 31 Mounting Orientation D horizontal with input on the left Fi...

Страница 24: ...24 Rockwell Automation Publication 1606 RM124A EN P September 2021 DC DC Converter 48V 48V 5 A 240 W Reference Manual Notes...

Страница 25: ...closures and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application I...

Страница 26: ...edgebase Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installat...

Отзывы: