DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual

The following recommendations are for building N+1 redundant power systems:

Keep a left/right installation clearance of 15 mm (0.6 in.) between two 
devices, and do not install the devices on top of each other. 

Do not use devices in parallel in mounting orientations other than the 
standard mounting orientation or in any other condition, where a 
reduction of the output current is required.

The ambient temperature cannot exceed 45 °C (113 °F).

Use In a Tightly Sealed 

Enclosure

When the device is installed in a tightly sealed enclosure, the temperature 
inside the enclosure is higher than outside. In such situations, the inside 
temperature defines the ambient temperature for the device.

In the following test setup, the device is placed in the middle of the enclosure, 
and no other heat-producing items are inside the enclosure. The load is placed 
outside the enclosure.

The temperature sensor inside the box is placed in the middle of the right side 
of the DC/DC converter with a distance of 1 cm (0.39 in.). The following 
measurement results can be used as a reference to estimate the temperature 
rise inside the enclosure.

Figure 26 - 1+1 Redundant Configuration for 5 A Load 

Current With a Dual Redundancy Module

Figure 27 - N+1 Redundant Configuration for 15 A Load Current With Multiple DC/DC 

Converters and Redundancy Modules

+

-

Functional

Earth

DC/DC

Converter

Input

Input

Output

Output

Input

1

Input ok

1

2

Input

2

Output

Optional

I

I

DC/DC

Converter

Redundacy

Module

Load

Failure

Monitor

Failure

Monitor

+

-

Functional

Earth

Output

Output

Output

Output

Optional

Optional

Input

Input

I

I

I

I

Output

Input

Input

Output

DC/DC

Converter

DC/DC

Converter

Redundacy

Module

Load

DC/DC

Converter

DC/DC

Converter

Redundacy

Module

Input

1

Input ok

1

2

Input

2

Input

1

Input ok

1

2

Input

2

Attributes

Values

Case A

Case B

Enclosure size

110 x 180 x 165 mm 

(4.33 x 7.09 x 6.50 in.)

Rittal Typ IP66 Box 

PK 9516 100, plastic

110 x 180 x 165 mm 

(4.33 x 7.09 x 6.50 in.)

Rittal Typ IP66 Box 

PK 9516 100, plastic

Input voltage

48V DC

48V DC

Load

48V, 4 A (=80%)

48V, 5 A (=100%)

Temperature inside the box

43.5 °C (110.3 °F)

48.1 °C (118.6 °F)

Temperature outside the box

26.2 °C (79.2 °F)

26.6 °C (79.8 °F)

Temperature rise

17.3 °C (31.1 °F)

21.5 °C (38.8 °F)

Содержание Allen-Bradley 1606-XLDF240F

Страница 1: ...DC DC Converter 48V 48V 5 A 240 W Catalog Number 1606 XLDF240F Reference Manual Original Instructions...

Страница 2: ...ell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission...

Страница 3: ...romagnetic Compatibility 13 Environment 14 Safety and Protection Features 15 Dielectric Strength 15 Approved Fulfilled or Tested Standards 16 Regulatory Product Compliance 16 Physical Dimensions and W...

Страница 4: ...4 Rockwell Automation Publication 1606 RM124A EN P September 2021 Table of Contents Notes...

Страница 5: ...DC output Efficiency up to 95 1 Width only 42 mm 1 65 in 20 output power reserves Full power between 25 60 C 13 140 F Soft start function Minimal inrush current surge Reverse input polarity protection...

Страница 6: ...x 4 88 x 4 61 in Without DIN rail Weight 500 g 1 1 lb Catalog Numbers Description 1606 XLDF240F DC DC converter 1606 XLC Wall or panel mount bracket see page 17 1606 XLA S44 Side mount bracket see pag...

Страница 7: ...led inside the device external capacitors on the input are allowed without any limitations External input protection The device is designed tested and approved for branch circuits up to 50 A without a...

Страница 8: ...his function increases the rise time of the output voltage by a small amount Output The output provides a SELV PELV rated voltage which is galvanically isolated from the input voltage and is designed...

Страница 9: ...t current Max 7 A Continuous current short circuit impedance 90 m Output capacitance Typ 1750 F Included inside the power supply Back feeding loads Max 63V The unit is resistant and does not show malf...

Страница 10: ...A 94 9 At 48V 6 A power boost Average efficiency Typ 94 6 25 at 1 25 A 25 at 2 5 A 25 at 3 75 A 25 at 5 A Power losses Typ 2 1 W At no output load 6 7 W At 48V 2 5 A 12 4 W At 48V 5 A 15 5 W At 48V 6...

Страница 11: ...inals screw terminals Dual terminals for the negative and positive pole Both poles are internally connected Positive output Negative return output 2 Output voltage potentiometer Open the flap to set t...

Страница 12: ...tical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product An MTBF value of for example 1 000 000 hr means that statistically one unit fails ever...

Страница 13: ...discharge 8 kV Criterion A Air discharge 15 kV Criterion A Electromagnetic RF field EN 61000 4 3 80 MHz 2 7 GHz 20V m Criterion A Fast transients Burst EN 61000 4 4 Input lines 4 kV Criterion A Outpu...

Страница 14: ...1 Shock and vibration are tested in combination with DIN rails according to EN 60715 with a height of 15 mm 0 59 in and a thickness of 1 3 mm 0 05 in These tests are performed with the DC DC converter...

Страница 15: ...input and PE measured with 500V DC Min 500 M At delivered condition between output and PE measured with 500V DC PE resistance Max 0 1 Resistance between PE terminal and the housing in the area of the...

Страница 16: ...he Council of June 1 2007 regarding the Registration Evaluation Authorization and Restriction of Chemicals REACH Ind Cont Eq Attributes Values and Descriptions Width 42 mm 1 65 in Height 124 mm 4 88 i...

Страница 17: ...ins the two brackets that are needed for one device Figure 22 Cat No 1606 XLC Wall Panel Mount Bracket Side Mount Bracket Cat No 1606 XLA S44 This bracket mounts the device sideways with or without us...

Страница 18: ...the perfect choice when the power supply has no DC OK function Two light emitting diode LEDs and two relay contacts signal when one of the two input voltages is not in range due to a non functioning...

Страница 19: ...discharged during such an event which causes a voltage dip on the output Figure 24 and Figure 25 show two typical voltage dips Output Circuit Breakers Standard miniature circuit breakers MCB s or UL 1...

Страница 20: ...DC must be installed with protection against touching Avoid return voltage for example from a decelerating motor or battery that is applied to the output terminals Keep a left right installation clea...

Страница 21: ...Redundancy Devices can be paralleled for 1 1 redundancy to gain higher system availability Redundant systems require a certain amount of extra power to support the load in case one device fails The si...

Страница 22: ...ide of the DC DC converter with a distance of 1 cm 0 39 in The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure Figure 26 1 1 Redundant Co...

Страница 23: ...28 Mounting Orientation A upright standard Figure 29 Mounting Orientation B upside down Figure 30 Mounting Orientation C table top Figure 31 Mounting Orientation D horizontal with input on the left Fi...

Страница 24: ...24 Rockwell Automation Publication 1606 RM124A EN P September 2021 DC DC Converter 48V 48V 5 A 240 W Reference Manual Notes...

Страница 25: ...closures and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application I...

Страница 26: ...edgebase Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installat...

Отзывы: