Rockwell Automation Publication 450L-UM001F-EN-P - March 2022
Chapter 5 System Configuration
The universal plug-in can be set to perform as an emitter or receiver. If pins 4
and 8 of the connectors are short circuited at power-up, the stick behaves like a
transmitter. In this case, the DIP switches have no functionality. Also, the
beam coding functionality is still set at the 450L-E Receiver (Rx). For the
confirmation of the beam coding configuration and the pairing procedure, see
Confirmation of a New System Configuration on page 59
. If pin 4 and pin 8 of
the plug-in are not short circuited at power-up, the corresponding stick
behaves like a receiver. In this case, the DIP switches have the same
functionality as the 450L-APR-ED-8 receiver plug-in.
Receiver Plug-in DIP Switch
Settings
The transmitter plug-ins and the cascading plug-ins don’t have DIP switches.
Identify and set the appropriate DIP switches for the configuration desired.
shows DIP switch identification. The number of DIP switches varies
depending on the plug-in type.
Figure 32 - DIP Switch Location at Receiver Plug-in
After installing the plug-in on the 450L-B safety light curtain transmitter stick
and power-up, a configuration confirmation can be performed (signaled by
the red/ green blinking of the STS status indicator). The confirmation of the
configuration can be performed without the receiver and transmitter aligned.
Table 22 - Functionalities Available for 450L PAC Safety Light Curtain
Description
Transmitter Plug-in
Receiver Plug-in
Universal Plug-in
450L-APT-PW-5
450L-APT-PW-8
ON/OFF
450L-APR-ON-5
EDM
450L-APR-ED-8
Muting
450L-APR-MU-8
450L-APU-UN-8
Number of Connection Pins
5
8
(1)
5
8
8
8
Number of DIP Switches
0
0
4
8
8
12
Low Range Activation
—
—
Start Mode Selection
—
—
—
EDM
—
—
—
Transmitter and Receiver Functionality
—
—
—
—
—
Blanking
—
—
—
—
—
—
Muting
—
—
—
—
—
Interference Rejection
(2)
—
—
Beam Coding
—
—
(1)
The 8-pin M12 for the transmitter is simply for the convenience of specifying two 8-conductor cordsets for the system.
(2) IR is always enabled in 450L PAC models, this is not user configurable.
IMPORTANT
DIP switches must be switched to OFF if the Switch Function is not
defined. Otherwise, an error condition occurs (see
).
After each reconfiguration of a safety light curtain, test the system for
proper configuration and operation before placing the guarded
machine in operation.
ATTENTION:
Every modification of the DIP switches must be confirmed with a
configuration confirmation procedure after the first power-up (see
Confirmation of a New System Configuration on page 59
ON
OFF
Содержание Allen-Bradley 140M
Страница 8: ...8 Rockwell Automation Publication 450L UM001F EN P March 2022 Table of Contents Notes ...
Страница 20: ...20 Rockwell Automation Publication 450L UM001F EN P March 2022 Chapter 2 Safety Concepts Notes ...
Страница 108: ...108 Rockwell Automation Publication 450L UM001F EN P March 2022 Chapter 7 Status Indicators and Troubleshooting Notes ...
Страница 114: ...114 Rockwell Automation Publication 450L UM001F EN P March 2022 Chapter 8 Safety Instructions Notes ...
Страница 184: ...184 Rockwell Automation Publication 450L UM001F EN P March 2022 Appendix B Typical Installations Notes ...
Страница 190: ...190 Rockwell Automation Publication 450L UM001F EN P March 2022 Index ...
Страница 191: ...Rockwell Automation Publication 450L UM001F EN P March 2022 191 GuardShield Safety Light Curtain User Manual ...