
3-36
Programming and Parameters
D
YNAMIC C
O
NTR
O
L
R
es
tar
t M
o
de
s
169 [Flying Start En]
Enables/disables the function which
reconnects to a spinning motor at actual
RPM when a start command is issued.
Default:
Options:
1
0
1
“Enabled”
“Disabled”
“Enabled”
When a drive is started in its normal mode, it initially applies a frequency of 0 Hz
and ramps to the desired frequency. If the drive is started into an already spinning
motor in this manner, without Flying Start enabled, large currents will be
generated and an overcurrent trip may result.
In Flying Start mode, the drive's response to a start command will be to identify
the motor's speed and apply a voltage that is synchronized in frequency,
amplitude and phase to the counter emf of the spinning motor. The motor will then
accelerate to the desired frequency.
170 [Flying StartGain]
Sets the response of the flying start
function.
Default:
Min/Max:
Units:
4000
20/32767
1
F
ile
Gr
oup
No
.
Parameter Name and Description
See
page 3-2
for symbol descriptions
Values
Re
lated
Содержание 9VT201-007HTNNN
Страница 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Страница 4: ...soc 2 ...
Страница 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Страница 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Страница 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Страница 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Страница 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Страница 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Страница 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Страница 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Страница 223: ......