Programming and Parameters
3-21
SPE
ED COMMA
N
D
Sp
d Mo
de
& L
imi
ts
089 [Logic Source Sel]
Selects the control source for the following
logic commands:
•
Start (Run)
•
Clear Faults
•
Stop
The All Ports selection allows ports to
control the logic command
simultaneously.
Default:
Options:
1
0
1
2
3
4
5
6
7
“Local OIM”
“Terminal Blk”
“Local OIM”
“DPI Port 2”
“DPI Port 3”
“Reserved”
“Network”
“Reserved”
“All Ports”
Important: The drive is shipped with a default configuration of control from the
keypad. For drive control from the terminal block inputs, set this parameter to
option 0 “Terminal Blk”.
Important: Asserting the terminal block input OIM Control overrides parameter
089.
Important: Asserting the Purge input overrides OIM Control and parameter 089.
F
ile
Gr
oup
No
.
Parameter Name and Description
See
page 3-2
for symbol descriptions
Values
Re
lated
!
ATTENTION: Setting parameter 089 to “Terminal Blk” or “Network”
while 168 [LevelSense Start] is enabled may start the drive if a start
command is on from the newly selected logic source.
ATTENTION: When 168 [LevelSense Start] is enabled, the user
must ensure that automatic start up of the driven equipment will not
cause injury to operating personnel or damage to the driven
equipment. In addition, the user is responsible for providing suitable
audible or visual alarms or other devices to indicate that this
function is enabled and the drive may start at any moment. Failure
to observe this precaution could result in severe bodily injury or
loss of life.
ATTENTION: Removing and replacing the LCD OIM while the
drive is running may cause an abrupt speed change if the LCD OIM
is the selected reference source, but is not the selected control
source. The drive will ramp to the reference level provided by the
OIM at the rate specified in 140 [Accel Time 1], 141 [Accel Time 2],
142 [Decel Time 1] and 143 [Decel Time 2]. Be aware that an
abrupt speed change may occur depending upon the new
reference level and the rate specified in these parameters. Failure
to observe this precaution could result in bodily injury.
ATTENTION: Note the following about stop commands:
•
A stop command from any attached OIM will always be enabled
regardless of the value of [Logic Source Sel].
•
Network stop commands are effective only when [Logic Source
Sel] is set to option 5 “Network” or 7 “All Ports”.
•
Terminal block stop commands are effective only when [Logic
Source Sel] is set to 0 “Terminal Blk” or 7 “All Ports”.
Failure to observe this precaution could result in severe bodily
injury or loss of life.
Содержание 9VT201-007HTNNN
Страница 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Страница 4: ...soc 2 ...
Страница 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Страница 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Страница 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Страница 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Страница 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Страница 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Страница 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Страница 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Страница 223: ......