1-6
Installation/Wiring
the cable between the transformer and drive or an additional transformer
or reactor. The impedance can be calculated using the information
supplied in Wiring and Grounding Guidelines for PWM AC Drives,
publication DRIVES-IN001.
The drive Safety Ground - PE must be connected to system ground.
Ground impedance must conform to the requirements of national and
local industrial safety regulations and/or electrical codes. The integrity
of all ground connections should be periodically checked.
For installations within a cabinet, a single safety ground point or ground
bus bar connected directly to building steel should be used. All circuits
including the AC input ground conductor should be grounded
independently and directly to this point/bar.
Figure 1.4 Typical Grounding
Safety Ground - PE
This is the safety ground for the drive that is required by code. This point
must be connected to adjacent building steel (girder, joist), a floor
ground rod or bus bar (see above). Grounding points must comply with
national and local industrial safety regulations and/or electrical codes.
Shield Termination - SHLD
) provides a grounding
point for the motor cable shield. The motor cable shield should be
connected to this terminal on the drive (drive end) and the motor frame
(motor end). A shield terminating cable gland may also be used.
When shielded cable is used for control and signal wiring, the shield
should be grounded at the source end only, not at the drive end.
General Grounding Requirements
U (T1)
V (T2)
W
(T3)
R
(L1)
S
(L2)
T (L3)
PE
S
HLD
Содержание 9VT201-007HTNNN
Страница 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Страница 4: ...soc 2 ...
Страница 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Страница 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Страница 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Страница 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Страница 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Страница 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Страница 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Страница 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Страница 223: ......