Terminal Connections
Chapter
6
Modem Connection
Wire or radio modem communication is possible between the
terminal and controller. Each modem must support full duplex
communication. Refer to your modem user manual for details on
settings and configuration.
Construct a Null Modem Cable
To construct a null modem cable, refer to this pinout.
Null Modem Pinout
PanelView
9-pin
9-pin
Modem
PanelView
9-pin
25-pin
Modem
FG (Frame Ground)
-
-
-
1
FG
TD (Transmit Data)
3
2
3
3
RD
RD (Receive Data)
2
3
2
2
TD
RTS (Request to Send)
7
8
7
5
CTS
CTS (Clear to Send)
8
7
8
4
RTS
SG (Signal Ground)
5
5
5
7
SG
DSR (Data Set Ready)
6
4
6
20
DTR
DTR (Data Terminal Ready)
4
6
4
6
DSR
PanelView Plus Compact Terminal
DF1 Port
Modem
Modem
Optical Isolator
Controller
Содержание 2711PC- T6C20D
Страница 6: ...6 Publication 2711PC UM001A EN P March 2009 Table of Contents ...
Страница 8: ...8 Publication 2711PC UM001A EN P March 2009 Preface ...
Страница 30: ...30 Publication 2711PC UM001A EN P March 2009 Chapter 3 Connecting Power ...
Страница 86: ...86 Publication 2711PC UM001A EN P March 2009 Chapter 5 Installing and Replacing Components ...
Страница 120: ...120 Publication 2711PC UM001A EN P March 2009 Appendix A Specifications ...
Страница 122: ...122 Publication 2711PC UM001A EN P March 2009 Appendix B USB Devices ...
Страница 126: ...126 Publication 2711PC UM001A EN P March 2009 Appendix C Available Fonts ...
Страница 129: ......
Страница 130: ......
Страница 131: ......