90
Publication 2711C-QS001F-EN-P - November 2010
Chapter 8
Create Alarms
4.
Click in the Alarm Type field
and select Numeric.
Verify that the Edge
Detection is Rising.
5.
Type 850 as the Value.
6.
Type MOTOR AT IDEAL
OPERATING SPEED! in
the Message field.
You can also click the ...
button in the Message field
to type the text in the text
dialog.
7.
Click the Add Alarm button
add to another alarm.
The second alarm is created
with many of the defaults
from the previous alarm.