Instruction Set
Relay
3-2
Relay Instructions
Instruction
Description
Examine On
XIC
Examine data table bit I:012/07, which corresponds to terminal 7 of an input module in I/O
rack 1, I/O group 2. If this data table bit is set (1), the instruction is true.
Examine Off
XIO
Examine data table bit I:012/07, which corresponds to terminal 7 of an input module in I/O
rack 1, I/O group 2. If this data table bit is reset (0), the instruction is true.
Output Energize
OTE
If the input instructions preceding this output instruction on the same rung go true, set (1) bit
O:013/01, which corresponds to terminal 1 of an output module in I/O rack 1, I/O group 3.
Output Latch
OTL
If the input conditions preceding this output instruction on the same rung go true, set (1) bit
O:013/01, which corresponds to terminal 1 of an output module in I/O rack 1, I/O group 3. This
data table bit remains set until an OTU instruction resets the bit.
Output Unlatch
OTU
If the input conditions preceding this output instruction on the same rung go true, reset (0) bit
O:013/01, which corresponds to terminal 1 of an output module in I/O rack 1, I/O group 3. This
is necessary to reset a bit that has been latched on.
I:012
] [
07
I:012
] / [
07
O:013
()
01
O:013
(L)
01
O:013
(U)
01