Troubleshooting
Extended Local I/O
5-36
The map table is corrupted.
Reenter the I/O map entry that is failing.
The target node of the MSG instruction is not a
processor or the target node of the CIO instruction
is not the correct I/O adapter.
Edit the ladder program so that the correct target
node is used.
Replace the target node with the correct type of
node.
12
0x000C
OBJECT IN WRONG STATE
The target Scheduled Peer Output map entry is
inhibited.
Clear the inhibit and immediate inhibit bits for the
target Scheduled Peer Output map entry.
14
0x000E
ATTRIBUTE CANNOT BE SET
A CIO instruction attempted to set an attribute that
cannot be set at the destination module. For
example, a CIO tried to send safe-state data to a
Flex module that does not support safe-state data.
Insert a module that can have this attribute set
into the correct slot.
Edit the ladder program so that it does not attempt
to set this attribute.
19
0x0013
NOT ENOUGH DATA
The transfer length is zero.
Increase the transfer length.
The processor data table is too small to hold the
data to be transferred.
Increase the size of the data table to
accommodate the transfer length.
21
0x0015
TOO MUCH DATA
The transfer length is too large.
Decrease the transfer length.
Decimal Code Hex. Code
Error Message
Explanation/Possible Cause(s)
Possible Corrective Action(s)
ControlNet Errors