Hardware Components
Processor Status File
1-16
processor status file continued...
This word of the status file:
Stores:
S:10
Minor fault (word 1)
Bit
Description
0
battery is low (replace in 1-2 days)
1
DH+ active node table has changed
2
STI delay too short, interrupt program overlap
3
EEPROM memory transfer at power-up
4
edits prevent SFC continuing; data table size changed
during program mode; reset automatically in run mode
5
invalid I/O status file
6
not defined
7
no more command blocks exist
8
not enough memory on the memory module to upload the program from the processor
9
no MCP is configured to run
10
MCP not allowed
11
PII word number not in local rack
12
PII overlap
13
no command blocks exist to get PII
14 arithmetic
overflow
15
SFC action overlap
See also S:17