3
Step 4
Mount the 1769-SM1 module.
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc.
Allow 50 mm (2 in.) of space on all sides for adequate ventilation as shown.
Allow at least 140 mm (5.5 in.) of enclosure depth to accomodate the
1769-SM1 module.
A. Panel Mounting — Mount the 1769-SM1 module to a panel using two
screws per module. Use M4 or #8 panhead screws. Mounting screws are
required on every module.
Using a Dimensional Drawing
NOTE: All dimensions are in mm (inches). Hole spacing tolerance:
± 0.04 mm (0.016 in.).
Figure 1 1769-SM1 Module with MicroLogix 1500 Base Unit and Processor
!
ATTENTION: Risk of equipment damage exists. During
panel or DIN rail mounting of all devices, be sure that all debris
(metal chips, wire strands, etc.) is kept from falling into the
1769-SM1 module. Debris that falls into the module could
cause damage on power up.
Compact I/O
Compact I/O
Compact I/O
Compact I/O
Compact I/O
End Cap or Cab
le
Controller
Top
Bottom
Side
Side
132 mm (5.19 in)
122.6 mm (4.83 in)
118 mm (4.65 in)
147.4 mm (5.81 in)
14.7 mm
(0.58 in)
35 mm
(1.38 in)
168 mm
(6.62 in)
147 mm
(5.79 in)
35 mm
(1.38 in)
13.5 mm
(0.53 in)
59 mm
(2.32 in)
59 mm
(2.32 in)
Mounting Hole
Dimension
DIN Rail
Center Line
28.5 mm
(1.12 in)
DPI / SCANport
MODULE
CH1
CH2
CH3
C
H
1
C
H
2
C
H
3