2

 

 

 

 

Step 2

Set the 1769-SM1 module Configuration Mode switch to an appropriate 
position. For complete switch setting details, see the 1769-SM1 module 
User Manual.

Step 3

Assemble the 1769-SM1 module to the controller. It can be attached to 
adjacent controller modules before or after mounting. For mounting 
instructions, see Step 4A (Panel Mounting) or Step 4B (DIN Rail 
Mounting). To work with a system that is already mounted, see Step 5.  

A. Disconnect power.

B. Install the 1769-SM1 module within 6 slots of the power supply.

C. Check that the bus lever (item 1) of the 1769-SM1 module is in the 

unlocked (fully right) position.

D. Use the upper and lower tongue-and-groove slots (item 2) to secure the 

modules together.

E. Move the 1769-SM1 module back along the tongue-and-groove slots 

until the bus connectors (item 3) line up with each other.

F. Use your fingers or a small screwdriver to push the bus lever back 

slightly to clear the positioning tab (item 4).

G. Move the 1769-SM1 module’s bus lever fully to the left (item 5) until it 

clicks. Ensure it is locked firmly in place.  

H. Attach an end cap terminator (item 6) to the last module in the system 

by using the tongue-and-groove slots as before.

I. Lock the end cap bus terminator (item 7).

Important: A 1769-ECR or 1769-ECL right or left end cap must be used 

to terminate the end cap of the serial communication bus.

7

6

5

4

2

1

2

3

!

ATTENTION:  Risk of equipment damage exists. When 
attaching the 1769-SM1 module to a Compact I/O system, it is 
very important that the bus connectors are securely locked 
together to ensure proper electrical connection. Failure to do 
this may cause an electrical arc, which can cause personal 
injury or equipment damage.

Содержание 1769-SM1

Страница 1: ...d machine motion Causing an explosion in a hazardous environment Electrical arcing causes excessive wear to contacts on both the module and its mating connector Worn contacts may create electrical resistance ATTENTION Risk of equipment damage exists The 1769 SM1 module contains ESD Electrostatic Discharge sensitive parts that can be damaged if you do not follow ESD control procedures Static contro...

Страница 2: ...ong the tongue and groove slots until the bus connectors item 3 line up with each other F Use your fingers or a small screwdriver to push the bus lever back slightly to clear the positioning tab item 4 G Move the 1769 SM1 module s bus lever fully to the left item 5 until it clicks Ensure it is locked firmly in place H Attach an end cap terminator item 6 to the last module in the system by using th...

Страница 3: ...ure 1 1769 SM1 Module with MicroLogix 1500 Base Unit and Processor ATTENTION Risk of equipment damage exists During panel or DIN rail mounting of all devices be sure that all debris metal chips wire strands etc is kept from falling into the 1769 SM1 module Debris that falls into the module could cause damage on power up Compact I O Compact I O Compact I O Compact I O Compact I O End Cap or Cable C...

Страница 4: ...unted modules d Drill and tap the mounting holes for the recommended M4 or 8 screw 132 mm 5 19 in 122 6 mm 4 83 in 118 mm 4 65 in 147 4 mm 5 81 in 14 7 mm 0 58 in 35 mm 1 38 in 35 mm 1 38 in 28 5 mm 1 12 in 35 mm 1 38 in 70 mm 2 76 in 35 mm 1 38 in 35 mm 1 38 in 35 mm 1 38 in 50 mm 1 97 in 40 mm 1 58 in 59 mm 2 32 in 59 mm 2 32 in Mounting Hole Dimension DIN Rail Center Line DPI SCANport MODULE CH...

Страница 5: ...a flat blade screwdriver D On the right side adjacent module move its bus lever to the right unlock to disconnect it from the module being removed E Gently slide the disconnected 1769 SM1 module forward If you feel excessive resistance make sure that you disconnected the module from the bus and that you removed both mounting screws or opened the DIN latches ATTENTION Risk of equipment damage exist...

Страница 6: ...2 C communications cable into a desired port CH1 CH2 or CH3 on the 1769 SM1 module B Plug the other male end of the cable into the port on the desired drive NOTE For EMC regulatory compliance there is a maximum cable distance limit per channel See the Regulatory Compliance section in the 1769 SM1 Compact I O to DPI SCANport Module User Manual for more information For general cable information see ...

Страница 7: ...r an initialization If the status indicators go red there is a problem Refer to the Troubleshooting chapter in the 1769 SM1 Compact I O to DPI SCANport Module User Manual Step 9 Read the 1769 SM1 Compact I O to DPI SCANport Module User Manual for information to configure and determine how to apply the network to the host product s ATTENTION Risk of equipment damage injury or death exists Unpredict...

Страница 8: ...x 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Power Control and Information Solutions Headquarters U S Allen Bradley Drives Technical Support Tel 1 262 512 8176 Fax 1 262 512 2222 Email support drives ra rockwell com Online www ab com support abdrives Publication 1769 IN083A EN P May 2012 P N 148231 Cop...

Отзывы: