70
Rockwell Automation Publication 1766-UM001O-EN-P - September 2021
Chapter 4 Communication Connections
For additional information on connecting the AIC+, see Advanced Interface
Converter (AIC+) User Manual
,
publication
.
Cable Selection Guide
1761-CBL-PM02
1761-CBL-AP00
Cable
Length
Connections from
to AIC+
External Power
Supply Required
(1)
Power Selection
Switch Setting
1761-CBL-AP00
(2)
1761-CBL-PM02
45 cm (17.7 in.)
2 m (6.5 ft)
SLC 5/03 or SLC 5/04 processors, ch 0
Port 2
Yes
External
MicroLogix 1200 ch 0
Port 1
Yes
External
MicroLogix 1400 ch 2
Port 2
Yes
External
PanelView 550
through NULL modem adapter
Port 2
Yes
External
DTAM™ Plus / DTAM™ Micro
Port 2
Yes
External
PC COM port
Port 2
Yes
External
(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to
cable
.
(2) Series C or later cables are required.
1761-CBL-HM02
(2)
1761-CBL-AM00
Cable
Length
Connections from
to AIC+
External Power
Supply Required
(1)
Power Selection
Switch Setting
1761-CBL-AM00
(2)
1761-CBL-HM02
45 cm (17.7 in.)
2 m (6.5 ft)
MicroLogix 1200 ch 0
Port 2
No
Cable
To port 2 on another AIC+
Port 2
Yes
External
(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to
cable
.
(2) Series C or later cables are required.
1761-CBL-AC00
1747-CP3
Cable
Length
Connections from
to AIC+
External Power
Supply Required
(1)
Power Selection
Switch Setting
1747-CP3
1761-CBL-AC00
3 m (9.8 ft)
45 cm (17.7 in.)
SLC 5/03 or SLC 5/04 processor, channel 0
Port 1
Yes
External
PC COM port
Port 1
Yes
External
PanelView 550 through NULL modem adapter
Port 1
Yes
External
DTAM Plus DTAM Micro
Port 1
Yes
External
Port 1 on another AIC+
Port 1
Yes
External
MicroLogix 1400 ch 2
Port 2
Yes
External
(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to
cable
.
user-supplied cable
Cable
Length
Connections from
to AIC+
External Power
Supply Required
(1)
Power Selection
Switch Setting
straight 9-25 pin
—
Modem or other communication device
Port 1
Yes
External
(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to
cable
.
Содержание 1766-L32AWA
Страница 10: ...10 Rockwell Automation Publication 1766 UM001O EN P September 2021 Table of Contents Notes ...
Страница 18: ...18 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 1 Hardware Overview Notes ...
Страница 56: ...56 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 3 Wire Your Controller Notes ...
Страница 122: ...122 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 5 LCD and Keypad Notes ...
Страница 152: ...152 Rockwell Automation Publication 1766 UM001O EN P September 2021 Appendix B Replacement Parts Notes ...
Страница 160: ...160 Rockwell Automation Publication 1766 UM001O EN P September 2021 Appendix C Troubleshoot Your System Notes ...
Страница 302: ...302 Rockwell Automation Publication 1766 UM001O EN P September 2021 Glossary Notes ...
Страница 308: ...308 Rockwell Automation Publication 1766 UM001O EN P September 2021 Index Notes ...