Appendix F MicroLogix 1400 Distributed Network Protocol
DNP3 Slave Application Layer Configuration Parameters
Channel for Unsolicited Response
Only channels already configured for DNP3 protocol appear in the Channel for
Unsolicited Response dropdown menu. Any and all Unsolicited Responses are
transmitted via this selected channel.
Channel 1 is only supported in MicroLogix 1400 Series B and Series C
controllers.
Valid selections are Enabled (Checked) and Disabled (Unchecked), with
disabled as default value.
Restore Events After Power Cycle
When the selection is Disabled (Unchecked), DNP3 events which are generated
before a power cycle are flushed after a power cycle. When the option is
Enabled (Checked), all DNP3 events are restored after a power cycle.
Enable Unsolicited On Start Up
Valid selections are Enabled (Checked) and Disabled (Unchecked). Default
value is Disabled (Unchecked).
When the selection is Disabled (Unchecked), the controller does not send any
enabled Unsolicited Responses after a restart until it has received a
FC_ENABLE_UNSOLICITED (20) command from the DNP3 Master.
When the selection is Enabled (Checked), the controller sends any enabled
Unsolicited Responses after a restart to the DNP3 Master unconditionally.
Enable Unsolicited For Class1
Valid selections are Enabled (Checked) and Disabled (Unchecked). Default
value is Disabled (Unchecked).
When the selection is Disabled (Unchecked), Unsolicited Response is disabled
for Class 1 events. To prevent overflowing of the event buffer, DNP3 Master
should poll for Class 1 events.
When the selection is Enabled (Checked), Unsolicited Response is enabled for
Class 1 events.
Enable Unsolicited For Class2
Valid selections are Enabled (Checked) and Disabled (Unchecked). Default
value is Disabled (Unchecked).
When the selection is Disabled (Unchecked), Unsolicited Response is disabled
for Class 2 events. To prevent overflowing of the event buffer, DNP3 Master
should poll for Class 2 events.
When the selection is Enabled (Checked), Unsolicited Response is enabled for
Class 2 events.
Enable Unsolicited For Class3
Valid selections are Enabled (Checked) and Disabled (Unchecked). Default
value is Disabled (Unchecked).
Содержание 1766-L32AWA
Страница 10: ...10 Rockwell Automation Publication 1766 UM001O EN P September 2021 Table of Contents Notes ...
Страница 18: ...18 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 1 Hardware Overview Notes ...
Страница 56: ...56 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 3 Wire Your Controller Notes ...
Страница 122: ...122 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 5 LCD and Keypad Notes ...
Страница 152: ...152 Rockwell Automation Publication 1766 UM001O EN P September 2021 Appendix B Replacement Parts Notes ...
Страница 160: ...160 Rockwell Automation Publication 1766 UM001O EN P September 2021 Appendix C Troubleshoot Your System Notes ...
Страница 302: ...302 Rockwell Automation Publication 1766 UM001O EN P September 2021 Glossary Notes ...
Страница 308: ...308 Rockwell Automation Publication 1766 UM001O EN P September 2021 Index Notes ...