Chapter 4 Communication Connections
Make a DF1 Point-to-Point Connection
You can connect the MicroLogix 1400 programmable controller to your
personal computer using a serial cable (1761-CBL-PM02) from your personal
computer’s serial port to the controller’s Channel 0. The recommended
protocol for this configuration is DF1 Full-Duplex.
You can connect a MicroLogix 1400 controller to your personal computer
directly without using an external optical isolator, such as Advanced Interface
Converter (AIC+), catalog number 1761-NET-AIC, as shown in the illustration
below, because Channel 0 is isolated within the controller.
Modem
You can use modems to connect a personal computer to one MicroLogix 1400
controller (using DF1 Full-Duplex protocol), to multiple controllers (using DF1
Half-Duplex protocol), or Modbus RTU Slave protocol via Channel 0, as shown
in the following illustration. See
for information on types of
modems you can use with the micro controllers.
Table 7 - Available Communication Cables
Communication Cables
Length
1761-CBL-AM00 Series C or later cables are required for Class I Div 2 applications.
45 cm (17.7 in.)
1761-CBL-AP00 Series C or later cables are required for Class I Div 2 applications.
45 cm (17.7 in.)
1761-CBL-PM02 Series C or later cables are required for Class I Div 2 applications.
2 m (6.5 ft)
1761-CBL-HM02 Series C or later cables are required for Class I Div 2 applications.
2 m (6.5 ft)
2707-NC9 Series C or later cables are required for Class I Div 2 applications.
15 m (49.2 ft)
1763-NC01 Series A or later
30 cm (11.8 in.)
1747-CP3 Series A or later
3 m (9.8 ft)
ATTENTION:
UNSUPPORTED CONNECTION
Do not connect a MicroLogix 1400 controller to another MicroLogix family
controller such as MicroLogix 1200 or to the 1747-DPS1 Network port using a
1761-CBL-AM00 (8-pin mini-DIN to 8-pin mini-DIN) cable or equivalent.
This type of connection will cause damage to the RS-232/RS-485 communication
port (Channel 0) of the MicroLogix 1400 and/or the controller itself.
Communication pins used for RS-485 communications are alternately used for
24V power on the other MicroLogix controllers and the 1747-DPS1 network port.
IMPORTANT
Do not attempt to use DH-485 protocol through modems under any
circumstance. The communication timing using DH-485 protocol is not
supported by modem communications.
MicroLogix 1400 channel 0
Personal
computer
1761-CBL-AP00 or
1761-CBL-PM02
1)
(1)
Series C or later cables are required for Class I Div 2 applications.
Содержание 1766-L32AWA
Страница 10: ...10 Rockwell Automation Publication 1766 UM001O EN P September 2021 Table of Contents Notes ...
Страница 18: ...18 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 1 Hardware Overview Notes ...
Страница 56: ...56 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 3 Wire Your Controller Notes ...
Страница 122: ...122 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 5 LCD and Keypad Notes ...
Страница 152: ...152 Rockwell Automation Publication 1766 UM001O EN P September 2021 Appendix B Replacement Parts Notes ...
Страница 160: ...160 Rockwell Automation Publication 1766 UM001O EN P September 2021 Appendix C Troubleshoot Your System Notes ...
Страница 302: ...302 Rockwell Automation Publication 1766 UM001O EN P September 2021 Glossary Notes ...
Страница 308: ...308 Rockwell Automation Publication 1766 UM001O EN P September 2021 Index Notes ...