Appendix F MicroLogix 1400 Distributed Network Protocol
Event Reporting
This section covers how to generate DNP3 events from DNP3 Data Objects and
how to report the generated events by polled response or unsolicited response.
Generate Events
The controller has a separate buffer area that you can use to log DNP3 events
internally.
The maximum number of the Events that can be logged is 6013 or 10000 (see
DNP3 10K Event Logging on page 250
), regardless of the Event data type. With
Series B and Series C controllers, a Data-Set event can consume multiple
numbers of the event buffers.
If the number of the generated events reaches this value, the controller sets
IIN2.3 [EVENT_BUFFER_OVERFLOW]. Further events are not logged until
the logged events are reported to DNP3 Master and the buffer is available.
The elements CS0:67 or CS2:67 in the Communication status file show how
many events are logged to the event buffer. The logged events are not removed
until they are reported to DNP3 Master successfully. Logged event can also be
cleared when one of the following events occur:
•
New OS firmware upgrade
•
New user program download.
shows how to generate events for a Binary Input Object and a 16-bit
Analog Input Object. In the DNP3 Slave configuration, Binary Input Object
Data File Number is configured to 10 and its Configuration File Number is
250
Read Only
VSTR
length of the
string value
length of the
string value
Device manufacturer's product
name and model
This variation returns
Catalog Number and OS
Series of the controller.
1766-L32BWA SER A.
This variation returns
Catalog Number and OS
Series of the controller.
1766-L32BWA SER B.
Supported ranges: 1766-L32xxxa SER y where xxxa is
BWA, AWA, BXB, BWAA, AWAA, or BXBA and y is A ~ F.
For example, 1766-L32BWA SER A, 1766-L32AWA SER
B, 1766-L32BXB SER C, or 1766-L32BWAA SER A.
251
-
-
-
-
Reserved for future assignment
-
-
252
Read Only
VSTR
13
19
Device manufacturer's name
This variation returns the
Company name. Allen-
Bradley.
This variation returns the
Company name. Rockwell
Automation for DNP3.
253
Read Only
-
-
-
Reserved for future assignment
-
-
254
Read Only
-
-
-
Non-specific all attributes request This variable returns all of the variations in this group
except this variation.
255
Read Only
-
-
-
List of attribute variations
This variation returns the R/W property for each
variation. From g0v211…g0v253.
0 for Read Only
1 for Read or Write
Object Group 0, Variations for Attribute Set 0 (Continued)
Variation
Read /Write Attribute
Data Type
Length in Bytes
(Series A)
Max Length in
Bytes (Series B
and Series C)
Description
Value (Series A)
Value (Series B)
Содержание 1766-L32AWA
Страница 10: ...10 Rockwell Automation Publication 1766 UM001O EN P September 2021 Table of Contents Notes ...
Страница 18: ...18 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 1 Hardware Overview Notes ...
Страница 56: ...56 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 3 Wire Your Controller Notes ...
Страница 122: ...122 Rockwell Automation Publication 1766 UM001O EN P September 2021 Chapter 5 LCD and Keypad Notes ...
Страница 152: ...152 Rockwell Automation Publication 1766 UM001O EN P September 2021 Appendix B Replacement Parts Notes ...
Страница 160: ...160 Rockwell Automation Publication 1766 UM001O EN P September 2021 Appendix C Troubleshoot Your System Notes ...
Страница 302: ...302 Rockwell Automation Publication 1766 UM001O EN P September 2021 Glossary Notes ...
Страница 308: ...308 Rockwell Automation Publication 1766 UM001O EN P September 2021 Index Notes ...