background image

SmartGuard 600 Controllers     

7

Publication 1752-IN001C-EN-P - January 2009

Before You Begin

Before you install the controller, set its DeviceNet node address and communication 
rate.

Set the Node Address

Use a small screwdriver to set the DeviceNet node address by using the two rotary 
switches on the front panel of the controller. Use care not to scratch the switches. 
Values from 00…63 are valid. The default setting is 63.

Follow these steps to set the node address.

1. Set the tens digit of the node address (decimal) by turning the left rotary 

switch.

2. Set the ones digit by turning the right rotary switch.

3. To set the node address by using RSNetWorx for DeviceNet software, set the 

rotary switches to a value from 64…99.

Setting the Communication Rate

The default communication rate for a DeviceNet network is 125 Kbps.

If you choose to use a different communication rate, the length of the trunkline and 
types of cable determine which communication rates your application can support.

IMPORTANT

Turn off power to the controller before setting the node address or communication rate 
via the switches.
Do not change the switch settings while the power supply is on. The controller will detect 
this as a change in the configuration and will switch to the ABORT mode.

IMPORTANT

A node address duplication error will occur if the same node address is set for more than 
one node.

DeviceNet Communication Rates and Cable Lengths

Communication 
Rate

Distance, Max

Cumulative Drop 
Line Length

Flat Cable

Thick Cable

Thin Cable

125 Kbps

420 m (1378 ft)

500 m (1640 ft)

100 m (328 ft)

156 m (512 ft)

250 Kbps

200 m (656 ft)

250 m (820 ft)

100 m (328 ft)

78 m (256 ft)

500 Kbps

75 m (246 ft)

100 m (328 ft)

100 m (328 ft)

39 m (128 ft)

Содержание 1752-L24BBB

Страница 1: ... 7 Set the Node Address 7 Setting the Communication Rate 7 Set the IP Address for Ethernet Communication 8 Install the SmartGuard 600 Controller 9 Mount the SmartGuard 600 Controller 9 Grounding the SmartGuard 600 Controller 10 Connecting a Power Supply 11 Wiring the SmartGuard 600 Controller 12 Making Communication Connections 15 Interpreting the Status Indicators 17 Alphanumeric Status Display 1...

Страница 2: ...ion Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited...

Страница 3: ...me Les combinaisons d équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l installation WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any extern...

Страница 4: ...read of flame complying with flame spread rating or 5VA V2 V1 V0 or equivalent if non metallic The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications In addition to this publication see Indust...

Страница 5: ... strip until after the controller and all the other equipment near the controller is mounted and wiring is complete Once wiring is complete remove the protective debris strip Failure to remove the strip before operating can cause overheating ATTENTION Serious injury may occur due to the loss of required safety function Do not use test outputs as safety outputs Do not use DeviceNet standard I O dat...

Страница 6: ...ation connector 7 Terminal connectors 8 Input status indicators 9 Output status indicators 10 Service switch Number Feature 1 Module status indicators 2 Alphanumeric display 3 Node address switches 4 Baud rate switches 5 USB port 6 DeviceNet communication connector 7 Terminal connectors 8 Input status indicators 9 Output status indicators 10 IP address display switch 11 Ethernet connector 12 Servi...

Страница 7: ...te The default communication rate for a DeviceNet network is 125 Kbps If you choose to use a different communication rate the length of the trunkline and types of cable determine which communication rates your application can support IMPORTANT Turn off power to the controller before setting the node address or communication rate via the switches Do not change the switch settings while the power su...

Страница 8: ... your network download the free Rockwell Automation BOOTP server from http www ab com networks bootp html To set the IP address by using the Rockwell Automation BOOTP utility follow these steps 1 Run the BOOTP utility 2 Double click the hardware address of the device you want to configure DIP Switch Settings DIPSwitch Pin 1 2 3 4 Communication Rate OFF OFF OFF OFF 125 Kbps ON OFF OFF OFF 250 Kbps ...

Страница 9: ...on ENET AP001 Install the SmartGuard 600 Controller To install the SmartGuard 600 controller you must mount it on the DIN rail wire the terminals and make communication connections Mount the SmartGuard 600 Controller IMPORTANT For effective cooling mount the controller on a horizontal DIN rail Do not mount the controller vertically provide a gap of at least 50 mm 2 0 in above and below the control...

Страница 10: ...two latches on the bottom of the controller Grounding the SmartGuard 600 Controller You must provide an acceptable grounding path for each device in your application Functionally ground the controller through its V0 G0 power connection In addition if you are using the 1752 L24BBBE controller you should connect the Ethernet ground terminal to an acceptable ground ATTENTION This product is grounded ...

Страница 11: ...owered by DC sources whose secondary circuits are isolated from the primary circuit by double insulation or reinforced insulation The DC power supply must satisfy the requirements for Class 2 circuits or limited voltage current circuits defined in UL 508 The SmartGuard controller has three V G terminal pairs that require a power connection There are two V0 G0 pairs but because they are internally ...

Страница 12: ...put circuits and test outputs V2 Power terminal for safety outputs G2 Power terminal for safety outputs IN0 IN15 Terminals for safety inputs T0 T3 These are test output terminals that can provide pulse test sources for safety inputs IN0 IN15 T3 can also support wire off detection and burned out bulb detection for a load such as a muting lamp OUT0 OUT7 Terminals for safety outputs WARNING If you co...

Страница 13: ...nect or disconnect the removable terminal block RTB while the field side power is applied an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding IMPORTANT Prepare stranded wires by attaching ferrules with plastic insulation covers compliant with the DIN 46228 4 standard Ferrules simil...

Страница 14: ...ety functions Do not connect loads beyond the rated value of safety or test outputs Do not use test outputs as safety outputs Wire the controller properly so that the 24V DC lines do not touch the safety or test outputs Do not apply the power supply to the test output terminals Ground the 0V line of the power supply for external output devices so that the devices do not turn on when the safety out...

Страница 15: ...ition you can communicate via the EtherNet IP network The EtherNet IP address and subnet mask are configured with the RSLinx module configuration The 1752 L24BBBE controller is shipped with BOOTP enabled for setting the IP Address See page 8 for details WARNING Do not connect or disconnect the communication cable with power applied to this controller or any device on the network because an electri...

Страница 16: ...ation connector to your personal computer when you want to configure the network and controller by using RSNetWorx for DeviceNet software Use a commercially available USB A to USB B male male cable to make the connection Wire No Wire Color Connects to 1 Red V 2 White CAN H 3 Drain 4 Blue CAN L 5 Black V ATTENTION The USB cable length must be less than 3 m 10 ft The USB port is intended for tempora...

Страница 17: ...alphanumeric status display for DeviceNet error codes DeviceNet node address and EtherNet IP address information ATTENTION The cable length must be less then 100 m 328 ft between hub and nodes WARNING If you connect or disconnect the Ethernet cable with power applied to this controller or any other device on this network an electrical arc can occur This could cause an explosion in hazardous locati...

Страница 18: ...guration signature to verify that the program and configuration of the controller has not been changed When the IP address display switch is pressed for 1 second or longer the display shows the EtherNet IP address that is set The error code n4 is displayed if an error occurs in the EtherNet IP configuration Status Indicators Use these tables to interpret the color and status combinations of the st...

Страница 19: ...Set the safety network number 3 Reconfigure the device DeviceNet Network Status NS D Indicator Descriptions If the DeviceNet Network Status NS D indicator is It means Take this action Off The controller is not online or may not have power from the DeviceNet network Refer to the corrective action following this table Green on The controller is online connections are established No action required G...

Страница 20: ...unication rate is the same for all nodes 4 Check that cables are not loose disconnected or too long 5 Verify that terminating resistors have been installed only at both ends of the main line 6 Take corrective action for noise 7 Make sure target devices are configured verified and in normal operating state Lock Configuration Lock Status Indicator Descriptions If the Lock Configuration Lock status i...

Страница 21: ...e specified range 2 Make sure a cable or wire is not disconnected USB Communication COMM U Status Indicator Descriptions If the USB Communication COMM U status indicator is It means Take this action Yellow flashing The controller is communicating No action required Off The controller is not communicating I O inputs 0 15 outputs 0 7 Status Indicators Descriptions If the I O status indicators are It...

Страница 22: ...tions If the EtherNet IP Network Status NS E indicator is It means Take this action Off The controller does not have an IP address or is not turned on Refer to the corrective action following this table Green flashing The controller has no established connections but has obtained an IP address Green on The controller has at least one established connection even to the message router No action requ...

Страница 23: ...ommunication rate is 100 Mbps No action required Off 1 1 If this indicator is Off along with the Network Speed 10 indicator check your Ethernet connection The communication rate is 10 Mbps Check that the Network Speed 10 indicator is on Ethernet Network Speed 10 Status Indicator Descriptions If the Ethernet Network Speed 10 status indicator is It means Take this action Yellow on The communication ...

Страница 24: ...with cyclic reconnecting Isolation voltage 50V Functional insulation type Tested at 600V AC for 60 s between all groups Wire type Copper Wiring category 2 2 on power signal and communication ports 2 on power 1 on signal 1 communication ports Wire size For power supply and I O use 0 2 2 5 mm2 12 24 AWG solid wire or 0 34 1 5 mm2 16 22 AWG standard flexible wire Before connecting prepare standard wi...

Страница 25: ...2 Auto negotiation Not applicable Supported Data rate Not applicable 10 100 Mbps Duplex Not applicable Full half Allowable unit communication bandwidth Not applicable 3000 pps 6 Explicit message communication Not applicable 502 Bytes 7 1 V0 G0 for internal logic circuit V1 G1 for external input devices and test outputs V2 G2 for external output devices 2 Use this Conductor Category information for...

Страница 26: ... 5 g 57 150 Hz IEC 60068 2 6 Test Fc Operating 5 g 10 500 Hz Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock 15 g Shock nonoperating IEC 60068 2 27 Test Ea Unpackaged Shock 30 g Enclosure type rating Meets IP20 Emissions CISPR 11 Group 1 Class A ESD immunity IEC 61000 4 2 4 kV contact discharges 8 kV air discharges IEC 61000 4 2 6 kV contact discharges 8 kV air discharges Radiated RF immun...

Страница 27: ...MHz Certifications Certification 1 when product is marked Value c UL us UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for US and Canada See UL File E194810 CE European Union 2004 108 EEC EMC Directive compliant with EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A B EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 ...

Страница 28: ... contact your local Rockwell Automation distributor or sales representative 1 See the Product Certification link at http ab com for Declarations of Conformity Certificates and other certifications details Resource Description SmartGuard 600 User Manual publication 1752 UM001 Information on wiring configuring operating and troubleshooting a SmartGuard 600 controller SmartGuard 600 Safety Reference ...

Отзывы: