SmartGuard 600 Controllers
25
Publication 1752-IN001C-EN-P - January 2009
Test output type
Current sourcing
Pulse test output current
(3)
0.7 A
Test output surge current
0.7 A
Pulse test off-state voltage, max
1.2V
Pulse test output leakage current,
max
0.1 mA
Muting lamp output current (T3)
•
More than 25 mA
•
Less than 5 mA
•
Normal operation (to avoid fault when used as a muting lamp
output)
•
Fault (a fault indication is generated when used as a muting
lamp output)
Output type
Current sourcing
Output current
0.5 A
Output surge current
0.5 A
Voltage, off-state output max
1.2V
Leakage current, off-state output,
max
0.1 mA
Heat dissipation
9.3 W under max load
Ethernet Communication
CIP connections
Not applicable
2
Auto negotiation
Not applicable
Supported
Data rate
Not applicable
10/100 Mbps
Duplex
Not applicable
Full/half
Allowable unit
communication bandwidth
Not applicable
3000 pps
(6)
Explicit message
communication
Not applicable
502 Bytes
(7)
(1) V0/G0 for internal logic circuit; V1/G1 for external input devices and test outputs; V2/G2 for external output devices.
(2) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication
1770-4.1
.
(3) T0...T3 total current at the same time: 1.4 A.
(4) Height includes terminal connectors.
(5) Depth includes DeviceNet connector.
(6) PPS is packets per second. It indicates the number of send or receive packets that can be processed per second.
(7) The maximum message length for class 3 connection and UCMM connection.
SmartGuard 600 Controllers - 1752-L24BBB, 1752-L24BBBE
Attribute
1752-L24BBB
1752-L24BBBE