Publication 1734-UM001D-EN-P - April 2008
Configure POINT I/O Modules in RSLogix 5000 Software
209
4.
From the Calibration dialog, click Start Calibration, which is active
when:
•
the system is online, and
•
you selected at least one of the channels.
Note that when you press the F1 button on your keyboard or click Help
from the wizards and warning messages that appear during calibration
you get detailed information about related procedures.
You see a Danger dialog.
5.
From the Danger dialog, for a module not currently used for control,
click OK.
You see a Low Value dialog.
6.
From the Low Value dialog, follow the instructions you see and click
Next.