Configure POINT I/O Modules in RSLogix 5000 Software
2.
From the Configuration dialog, complete entries, referring to the table.
3.
From the bottom of the Configuration dialog, perform one of the
following:
•
Click another tab at the top of the dialog.
or
•
Click OK to save changes and close the dialog.
or
•
Click Cancel to return to default values.
or
•
Click Apply to save changes you made on any of the dialogs and
continue to display the dialog, noting that you enable the Apply
button when you make changes to any of the dialogs.
For This Value
Select
Comments
High Engineering
-32768…32767
•
Default for 1734-OE2C analog output module is 8191.
•
Default for 1734-OE2V analog output module is 10000.
Low Engineering
-32768…32767
•
Default for 1734-OE2C analog output module is 1638.
•
Default for 1734-OE2V analog output module is 0.
Current Range
4…20 mA
0…20 mA
Default is 4…20 mA.
Voltage Range
-10…10V
0…10V
Default is 0…10V