Publication 1734-UM001D-EN-P - April 2008
160
Troubleshoot with the Indicators
1734-APB PROFIBUS Adapter
Adapter
Status
PROFIBUS
Status
PointBus
Status
1734-APB
Field
Power
System
Power
System Power
Field Power
Adapter Status
PROFIBUS Status
POINTBus Status
1734-2
Indication
Probable Cause
Recommended Action
Adapter Status
Off
•
No power supplied.
•
Hardware check is in progress.
•
Initialization is in progress.
1. Apply power.
2. Wait for power self-test to complete.
Green
Operation is normal.
None.
Red
Hardware check fault present.
Replace device.
Indication
Probable Cause
Recommended Action
PROFIBUS Status
Off
No power supplied.
Bus is offline.
Apply power, verify network cabling, and correct,
as needed.
Solid green
Bus is online (data exchange).
None.
Flashing green
Adapter received a CLEAR command from the master.
None.
Solid red
Error in PROFIBUS initialization is present.
No modules installed in the backplane.
Verify configuration, proper installation of
modules, and correct, as needed.
Flashing red
1 Hz - Check_Configuration telegram rejected.
Max number of POINT I/O modules in master configuration
overridden.
2 Hz - SetPrm telegram rejected.
The first byte in user parameter data does not equal zero.
Max number of user parameter bytes overridden.
Check configuration.
Содержание 1734-IA2
Страница 4: ...Publication 1734 UM001D EN P April 2008 4 Summary of Changes Notes ...
Страница 12: ...Publication 1734 UM001D EN P April 2008 12 Table of Contents Notes ...
Страница 77: ...Publication 1734 UM001D EN P April 2008 Install POINT I O Modules 77 ...
Страница 78: ...Publication 1734 UM001D EN P April 2008 78 Install POINT I O Modules ...
Страница 179: ...Publication 1734 UM001D EN P April 2008 Default Data Maps 177 Notes ...
Страница 180: ...Publication 1734 UM001D EN P April 2008 178 Default Data Maps ...
Страница 236: ...Publication 1734 UM001D EN P April 2008 234 Notes ...
Страница 241: ......