Publication 1734-UM001D-EN-P - April 2008
Calibrate Your Analog Modules
123
Calibrate the Analog
Current Input Module
To calibrate your current input module, connect the module in a system
similar to that shown in the figure.
.
IMPORTANT
Apply power to the power supply and module for at least 10
minutes before calibrating the module. This allows internal
temperatures to stabilize, and reduces drift errors.
0
1
0
1
0
1
0
1
0
1
0
1
PDN IE2C
250
Ω
Current Source
DeviceNet Input
44035
Power Supply Voltage
Channel 0
Connect to 0 and 4
Channel 1
Connect to 1 and 5
250
Ω
resistor
protects the current
source in the event
of shorted wires.
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Module
Status
Network Activity
Status
Network
Status
1734-AENT
PointBus
Status
Field
Power
System
Power
0 2
0
AENT IE2C
EtherNet/IP Input
44037
Current Source
Power Supply Voltage
250
Ω
Channel 0
Connect to 0 and 4
Channel 1
Connect to 1 and 5
250
Ω
resistor
protects the current
source in the event
of shorted wires.
Содержание 1734-IA2
Страница 4: ...Publication 1734 UM001D EN P April 2008 4 Summary of Changes Notes ...
Страница 12: ...Publication 1734 UM001D EN P April 2008 12 Table of Contents Notes ...
Страница 77: ...Publication 1734 UM001D EN P April 2008 Install POINT I O Modules 77 ...
Страница 78: ...Publication 1734 UM001D EN P April 2008 78 Install POINT I O Modules ...
Страница 179: ...Publication 1734 UM001D EN P April 2008 Default Data Maps 177 Notes ...
Страница 180: ...Publication 1734 UM001D EN P April 2008 178 Default Data Maps ...
Страница 236: ...Publication 1734 UM001D EN P April 2008 234 Notes ...
Страница 241: ......