1606-XLE80E-2 24V, 3.3A; Single Phase Input
10000108328
(Version 00)
www.ra.rockwell.com
Page 5
7.
I
NPUT
I
NRUSH
C
URRENT
S
URGE
A NTC limits the input inrush current after turn-on of the input voltage. The charging current into EMI suppression capacitors is disregarded in the first
microseconds after switch-on.
AC 100V
AC 120V
AC 230V
Inrush
current
max. 24A
peak
28A
peak
54A
peak
At 40°C cold-start
typ. 20A
peak
23A
peak
45A
peak
At 40°C cold-start
Inrush
energy
typ. 0.4A
2
s 0.5A
2
s 1.7A
2
s
At 40°C cold-start
Fig. 7-1 Input inrush current, typical behavior
Input Current
Input Voltage
Output Voltage
A:
Start-up delay = Inrush delay
Input:
230Vac
Output: 24V, 3.3A
Ambient: 25°C
Upper curve:
Input current 20A / DIV
Medium curve:
Input voltage 500V / DIV
Lower curve:
Output voltage 20V / DIV
Time scale:
40ms / DIV
8.
H
OLD
-
UP
T
IME
AC 100V
AC 120V
AC 230V
Hold-up Time
typ.
38ms
60ms
244ms
1.65A, 24V, see
Fig. 8-1
typ.
19ms
29ms
120ms
3.3A,
24V,
see
Fig. 8-1
Fig. 8-1 Hold-up time vs. input voltage
Fig. 8-2 Shut-down behavior, definitions
0
25
50
75
100
225ms
85
120
155
190
230Vac
Input Voltage
125
150
175
Hold-up
Time
200
24V, 3.3A, min.
24V, 3.3A, typ.
24V, 1.65A, min.
24V, 1.65A, typ.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Intput
Voltage
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is on during this time.