Rockwell
Automation
1606-XLE80E-2 24V, 3.3A; Single Phase Input
10000108328
(Version 00)
www.ra.rockwell.com
Page 6
9.
O
UTPUT
Output
voltage
nom. 24V
Adjustment
range
min. 24-28V
Guaranteed
max.
30V
At clockwise end position of potentiometer
Factory
setting
24.1V
±0.2%,
at full load, cold unit
Line
regulation
max.
50mV
90 to 264Vac
Load
regulation
max. 100mV
Static
value,
0A
Æ
3.3A
Æ
0A
Ripple and noise voltage
max.
50mVpp
20Hz to 20MHz, 50Ohm
Output
capacitance
typ. 1
450µF
Output current
nom.
3.3A
At 24V, see Fig. 9-1
nom.
2.7A
At 28V, see Fig. 9-1
Output
power
nom. 80W
Short-circuit
current
min.
4A
Load impedance 250mOhm, see
Fig. 9-1
max.
8A
Load impedance 250mOhm, see
Fig. 9-1
Fig. 9-1 Output voltage vs. output current, typ.
Output Voltage
0
0
4
4
8
12
28V
16
20
24
7A
6
2
1
3
5
Adjustment
Range
Output Current
a) 100Vac
b) 120Vac
c) 230Vac
a
b
c
Peak current capability (up to several ms)
The power supply can deliver a peak current which is higher than the specified short term current. This helps to start current demanding loads or to
safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be discharged and causes a voltage
dip on the output. Detailed curves can be found in chapter 26.1.
Peak current voltage dips
typ.
from 24V to 12.5V
At 6.6A for 50ms, resistive load
typ.
from 24V to 12.5V
At 16.5A for 2ms, resistive load
typ.
from 24V to 7V
At 16.5A for 5ms, resistive load