1606-XLE80E-2 24V, 3.3A; Single Phase Input
10000108328
(Version 00)
www.ra.rockwell.com
Page 16
24.
I
NSTALLATION AND
O
PERATION
I
NSTRUCTIONS
Hazardous voltage inside device. Risk of electric shock, severe burns, or death.
•
Do not use the unit without proper earth connection (Protective Earth). Use the pin on the terminal block for earth connection and not one of
the screws on the housing.
•
Turn power off before working on the power supply. Protect against inadvertent re-powering.
•
Make sure the wiring is correct by following all local and national codes.
•
Do not open, modify or repair the unit.
•
Use caution to prevent any foreign objects from entering into the housing.
•
Do not use in wet locations or in areas where moisture or condensation can be expected.
Mounting Orientation:
Output terminal must be located on top and input terminal on the bottom. For other orientations see section 26.12
Cooling:
Convection cooled, no forced cooling required. Do not cover ventilation grid (e.g. cable conduits) by more than 30%!
Installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent
device is a heat source, 15mm clearance is recommended.
Service parts:
The unit does not contain any serviceable parts. The tripping of an internal fuse is caused by an internal defect.
25.
A
CCESSORY
1606-XLB Wall mounting bracket
This bracket is used to mount XLE units onto a flat surface without utilizing a DIN-Rail. The two aluminum brackets and the black plastic slider of the
unit have to be detached, so that the two steel brackets can be mounted.
(Picture shows a different power supply)
Fig. 25-1 1606-XLB Wall Mounting Bracket
Fig. 25-2 Assembled Wall Mounting Bracket