2.0 FIRST BOILER START UP
1.
There is function called First boiler start up which is functuon used for exact setup of main boiler
functions. Installer is responsible for this setup. First boiler start up has to be done before turning
on the burner for the first time.
a.
Time
2.
Set real time. Some features as Time table, history or online functions needs time for running
properly.
a.
Date
3.
Set real date, which is used in the same functions as shown abowe.
a.
Burner size
4.
Burner size is responsible for exact auger run times during PID work. So you have to set it correctly.
Check burner package, or sticker which is on the burner to be sure that the size in Kw is correct.
5.
Burner size changes values in Service settings shown below:
6.
Auger setup, Ignition:
a.
Feed time – for how long pellet auger supplies pellets on the burner grate
b.
Fan speed – speed of the fan during ignition phase.
c.
Lumidity – fire sensor sensitivity. Lower number means higher sensitivity.
7.
Auger setup, Work:
a.
Feeder time min – auger run time for minimum power
b.
Feeder interval max – auger wait time for minimum power
c.
Feeder time max – auger run time for maximum power
d.
Feeder interval min – auger wait time for maximum power
e.
Min fan speed – speed of the fan during minimum power
f.
Max fan speed – speed of the an during maximum power
8.
Auger setup, Extinction:
a.
Extinction time – fan works all the time during this process and tries to clean all ashes from
the grate
b.
Fan speed – speed of the fan during extinction phase.