2.0 FIRST BOILER START UP 

1.

 

There is function called First boiler start up which is functuon used for exact setup of main boiler 
functions. Installer is responsible for this setup. First boiler start up has to be done before turning 
on the burner for the first time.  

 

a.

 

Time 

2.

 

Set real time. Some features as Time table, history or online functions needs time for running 
properly.  

 

a.

 

Date 

3.

 

Set real date, which is used in the same functions as shown abowe.  

 

a.

 

Burner size 

4.

 

Burner size is responsible for exact auger run times during PID work. So you have to set it correctly. 
Check burner package, or sticker which is on the burner to be sure that the size in Kw is correct.  

5.

 

Burner size changes values in Service settings shown below: 

6.

 

Auger setup, Ignition: 

a.

 

Feed time – for how long pellet auger supplies pellets on the burner grate 

b.

 

Fan speed – speed of the fan during ignition phase.  

c.

 

Lumidity – fire sensor sensitivity. Lower number means higher sensitivity.  

7.

 

Auger setup, Work: 

a.

 

Feeder time min – auger run time for minimum power 

b.

 

Feeder interval max – auger wait time for minimum power 

c.

 

Feeder time max – auger run time for maximum power 

d.

 

Feeder interval min – auger wait time for maximum power 

e.

 

Min fan speed – speed of the fan during minimum power 

f.

 

Max fan speed – speed of the an during maximum power 

8.

 

Auger setup, Extinction: 

a.

 

Extinction time – fan works all the time during this process and tries to clean all ashes from 
the grate 

b.

 

Fan speed – speed of the fan during extinction phase.  

Содержание Biopel 15

Страница 1: ...Biopel Pellet Boiler Installation manual...

Страница 2: ...ibed here in this manual It is recommended to study the menus prior to initial start Save this manual so you always have it available when needed Page 3 Comments on the Manual Page 4 The Clean Air Act...

Страница 3: ......

Страница 4: ......

Страница 5: ...se countries Separate legislation the Clean Air Northern Ireland Order 1981 applies in Northern Ireland Therefore it is a requirement that fuels burnt or obtained for use in smoke control areas have b...

Страница 6: ...uts as the seal between the boiler and the burner can leak over time 4 Make sure that the burner is horizontal and that all connections are tight Burner description The main parts of the burner are th...

Страница 7: ...ler for burner installation However the opposite flange on the boiler bust be always sealed For example if you choose left flange for burner connection make sure that right flange is properly sealed B...

Страница 8: ...le located on the top of the burner and secure with 2 x burner pipe screws Attach PVC tube on the burner pipe and from the other side on the external auger outlet You can cut the PVC tube if necessary...

Страница 9: ...nt ignition of the boiler and will prolong the life of the igniter The min buffer thermal store capacity should be 10 litres kW output eg 200 litres for Biopel 20 The load valve supplied with the boil...

Страница 10: ...and connection board are pre wired with simple plugs to allow for quick installation When using the Compact type hopper the connection board can be fixed to the sloping wall of the hopper near the bur...

Страница 11: ...is the boiler pump ROOM REGULATOR Room thermostat volt free Other connections for optional accessories are DHW PUMP Used to control a pump or 2 port valve for hot water production KOMPRESSOR Connecti...

Страница 12: ......

Страница 13: ...t is designed to offer the home owner and installer a series of simple menus to give full control of all boiler settings and parameters The controller has 3 levels of PIN protection in order to preven...

Страница 14: ...he same time o Summer mode sets the burner power to an half value To be specific Feed time max and Feed interval min is reduced to half Cleaning cleaning of the grate during PID modulation work o Acti...

Страница 15: ...rrection correction of fan speed 50 Power factor correction of burner power Changes values in Feedertimemax and Feeder interval min in range of 50 Example if you set 30 in Augercorrection 30 it means...

Страница 16: ...at the size in Kw is correct 5 Burner size changes values in Service settings shown below 6 Augersetup Ignition a Feed time for how long pellet auger supplies pellets on the burner grate b Fanspeed sp...

Страница 17: ......

Страница 18: ...for PID regulation is lower which means speed of the fan is decreased in all PID modulation range Power correction Power correction is responsible for changing number of pellets going on the grate Yo...

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ...r is obligated to check the goods immediately upon receipt If the buyer declares that the delivery was inadequate or defective the customer must immediately and without delay make a written claim with...

Страница 23: ......

Отзывы: