Heating engineer
Installation, use and maintenance manual – Calorio M
11
3
2.3.1
Where to install the appliance
▶
The gas-fired convector must be installed on or near
an external perimeter wall, respecting the distances
indicated in Figure 1.1
▶
Avoid placement on walls or combustible materials
without a suitable heat shield.
▶
Do not install the gas-fired convector over electrical
boxes/switches or distribution cabinets that require
periodic inspection.
Installation must not be made on walls with poor
strength that do not guarantee adequate resist-
ance to the stresses produced by the appliance.
The manufacturer assumes no responsibility if the
appliance is installed on surfaces or walls that are
not suitable to support its weight.
The appliance's flue gas exhaust must not be im-
mediately close to openings or air intakes of build-
ings, and must comply with safety and environ-
mental regulations.
The flue gas exhaust terminal is accident-pre-
venting and requires no protection.
2.4
MINIMUM CLEARANCE DISTANCES
2.4.1
Distances from combustible or flammable
materials
▶
Keep the appliance away from combustible or flam-
mable materials or components, in compliance with
applicable regulations.
2.4.2
Clearances around the appliance
The minimum clearance distances are required for
safety, operation and maintenance.
▶
The minimum recommended distance from the gas-
fired convector to the floor is 5 cm (Figure 1.1
and possibly not more than 35 cm, as higher heights
would result in uneven heat distribution in the heated
room.
▶
Keep a minimum clearance of 10 cm from the sides of
the gas-fired convector to any obstacles to allow for
removal and refitting of the casing.
▶
If a shelf is to be installed above the gas-fired convec-
tor, leave a minimum clearance of 10 cm. No cover of
any type may be installed over the appliance.
3
HEATING ENGINEER
3.1
WARNINGS
3.1.1
General warnings
Read the warnings in Chapter III.1
p. 4, pro-
viding important information on regulations and
on safety.
Compliance with installation standards
Installation must comply with applicable regula-
tions in force, based on the installation Country
and site, in matters of safety, design, implementa-
tion and maintenance of:
heating systems
gas systems
flue gas exhaust
Installation must also comply with the manufactur-
er's provisions.
3.2
SUPPLIED MATERIAL
▶
Installation jig in cardboard.
▶
Wall support bracket.
▶
Air duct Ø 49 mm, length 500 mm.
▶
Flue gas duct Ø 35 mm, length 500 mm.
▶
External flue gas terminal in aluminium alloy.
▶
Round gasket for combustion air.
▶
Screws and wall plugs.
▶
Documentation.
3.3
FUEL GAS SUPPLY
3.3.1
Gas connection
▶
1/2" M
on the right, at the bottom (detail A in Figure 3.1
▶
Install an anti-vibration connection between the ap-
pliance and the gas piping.