figure 3�4
horizontal tube slope.
LeGend
p(%)
tube slope *
* slope to be provided: -2% or -3% (downwards).
example:
slope (downwards) of 2 cm per metre or 3 cm per metre
p(%)
If the fumes tubes are vertical, to prevent condensation from returning to the appliance,
equip the base of the vertical tube with a "T" junction to collect the condensate (see ex-
ample "B" in Figure 3.5
→
17).
figure 3�5
B23 type installations: with wall-mounted exhaust and roof-mounted exhaust.
LeGend
A
type B23 installation with hori-
zontal exhaust (or wall-mounted)
[B15 generator: seen from above]
B
type B23 installation with vertical
exhaust (or roof-mounted)
[B15 generator: side view]
1
combustion air intake
2
fumes exhaust
3
condensation outlet
1
2
A
3
2
B
B15
B15
table 3�1
dAtA foR CALCULAtInG tHe AIR/fUMes sYsteM WItH CoMMeRCIALLY AVAILABLe tUBes
Fumes outlet temperature [°C]
Fumes mass flow rate [kg/h]
CO
2
content of fumes [%] (with
G20 gas)
Admitted pressure drop [Pa]
175
25,9
9,2 ÷ 9,4
60
Data for calculating the air/fumes system with commercially available tubes.
table 3�2
PRESSURE DROP OF DIA. 80 COMPONENTS
PRessURe dRoP of dIA� 100 CoMPonents
tube [Pa/m]
90° bend [Pa]
coaxial [Pa]
tube [Pa/m]
90° bend [Pa]
coaxial [Pa]
fumes air
fumes air
wall
O-SCR007
roof
O-SCR008
fumes air
fumes air
roof O-SCR009
0,7
0,4
1,0
0,9
1,6
2,0
0,2
0,2
0.35
0,25
1,0
Dati per il calcolo del sistema aria/fumi con condotti Ø 80 o Ø 100 forniti da Robur Spa.