ROBOVENT • DFS SERIES OWNER’S MANUAL
A-8
APPENDIX A
ePad Operator Instructions
(continued)
PULSE CONTROL SETTINGS
There are (3) different Pulse Modes. Online
(while running, Offline (after shutdown)
and Maintenance (at select times to
maximize filter life).
Online:
Filters are pulsed while unit is
running. The typical value settings are
shown.
Offline:
Filters are pulsed after blower(s)
are shutdown. The typical value settings
are shown.
Maintenance:
Filters are pulsed for an
extended period, for maximum cleaning.
The typical value settings are shown.
Delay Time:
amount of time (in seconds)
between pulses.
Pulse Time:
amount of time (in
milliseconds) that pulse valve is open.
Usually set at 200msec. (Note: the right
hand zero is fixed, so enter 20 for 200).
Post Cycles:
number of times each filter
bank is pulsed after blower shutdown.
Important Note: Supervisory
Maintenance Security Level is
required to access these screens.