ROBOVENT • DFS SERIES OWNER’S MANUAL
24
SECTION 800
Filter Change Maintenance Procedure
(continued)
the collector as far as you can reach. Upon completion, reconnect the duct to its original
configuration.
10. Access the filter cabinet to continue the cleaning of the unit. The goal is to remove all
pockets of built up particulate.
Note:
Monitor the dust tray from time to time to verify that it is not overflowing.
11. Remove and empty the dust tray. Observe thru the dust tray slot that all particulate has
been removed. If pockets of particulate are present, they should be vacuumed up to
prevent it from reentering onto the new filters. Reinstall the dust tray.
12. Place the new cartridge filters into the dust collector. The filters have metal end caps.
The bottom has a rubber gasket. They must be installed in this configuration only to
ensure a proper seal. Place the 1st (bottom) filter on center, over the “seat” or opening.
The filter will be level and stable (no rocking) when properly set. Look down through the
center of the filter to verify uniformity to the filter “seat” inner ring and opening. Place
the 2nd filter evenly over the 1st filter and place a top pan, centered on top of the filter
stack. The T-handle filter tightening mechanism will turn (right to left) and make contact
with the indentation on the center of the top pan. Sometimes a slight movement of the
filter stack is necessary to center the T-handle/top pan. When T-handle/top pan contact is
made, continue turning (roughly 14-18, 1⁄2 turns) until the filter stack is properly installed.
To verify proper installation, place your hand on the seam of the 2 filters in the middle
and push on the seam. There should be very little or no movement noticed. Continue this
procedure until all filters are installed.
Note:
The gasket will usually compress to a gap of 1/4” to 3/8” when properly installed.
13. Close and secure the filter door.
14. Turn on the main power disconnect.
Note:
Anytime that the filter access door is open, the main power disconnect should be
turned off. This is to prevent random solenoid firing of the compressed air through the
cleaning mechanism. This should also be done while looking into the dust tray slot.
15. Turn on the collector and record the new
∆
P/Static Pressure.
16. Open the petcock valve on the solenoid accumulator and verify that there is not moisture
in the compressed air stream.
Note:
Any oil visible in the accumulator will be blown into the system and onto the filters
causing premature filter failure. Water, though not preferred is less damaging and will
evaporate over time. A lot of water may necessitate shutdown of the collector so as to not
damage the paper filter pleats.
Содержание FloorSaver Series
Страница 2: ......
Страница 29: ...ROBOVENT FUSION 4 5 SERIES OWNER S MANUAL 65 SECTION 1000 Motor Greasing Guide ...
Страница 38: ...ROBOVENT DFS SERIES OWNER S MANUAL ...
Страница 41: ...APPENDIX A ePad Electronic Programmable Controller Instruction Manual ...
Страница 51: ...APPENDIX B General Wiring Diagram ...
Страница 52: ...B 1 ROBOVENT DFS SERIES OWNER S MANUAL APPENDIX B General Wiring Diagram Single Blower ...
Страница 53: ...ROBOVENT DFS SERIES OWNER S MANUAL B 2 APPENDIX B General Wiring Diagram Double Blower ...
Страница 54: ......
Страница 55: ...APPENDIX C Parts List ...
Страница 58: ......
Страница 59: ......