Output power per relay:
Total output power (all relays):
Power supply:
Ingress protection:
Operating temperature:
Storage temperature:
Relative humidity:
Dimensions:
Weight:
Standards:
Maximum input cable length:
200W
2000W
50m
24V
60mA
IP20
0..45°C
-20..75°C
0..95% n/c
106x108x58mm
250g
EN 60730-1
QX0U
up
up
up
up
up
up
up
up
up
up
QX2U
IX0U
IX2U
0V
L
+24V
QX0D
dn
dn
dn
dn
dn
dn
dn
dn
dn
dn
QX2D
C
C
QX1U
QX3U
QX4U
IX0D
IX2D
QX1D
QX3D
QX4D
IX1D
IX3D
IX4D
C
C
C
IX1U
IX3U
IX4U
230VAC
BC-5-IQ blinds controller
Mounting: 35mm DIN rail 6M
106
up and down buton
automatic correction
at boundary position
5-channel blinds position controller
short press while moving: stop at the position
long press: stop after released
short press: move to intermediate position
automatic position related to scene
75%
Features
short press: move up/down
37
Hardware
1. Adjust top and bottom limit switch (electrician).
2. Use stopwatch to measure travel time in both directions.
3. Use HIQ Configurator to enter measured values.
4. Check accuracy: move blinds to 50%, mark position. Move
blinds about half way up and down, few times, without
reaching the top or bottom. Move to 50% again. If the actual
position is above the mark, slightly increase down time. Below
the mark, increase up time. Repeat until positioning is perfect.
Travel time adjustment
Technical specifications
Содержание HIQ Home
Страница 1: ...User Manual v1 3 1 HIQ Home...