SECTION 10: W
IRING
59
SECTION 10: WIRING
Heaters can be controlled using several methods.
Normally thermostats are used to control the heaters
but they can also be controlled by an Energy
the connection for heaters controlled by a line voltage
thermostat. NOTE: In order to use line voltage ther
-
mostats, the low voltage terminal located at the back
of each burner must be connected as shown in the
detail. For a single heater on a low voltage thermo
-
stat,
heaters on one low voltage thermostat,
. NOTE: In order to control multiple heat
-
ers on one low voltage thermostat, the low voltage
terminals on each heater must be connected as
shown in detail. Heater must be grounded in accor
-
dance with applicable codes:
United States:
refer to
National Electrical Code
®
NFPA 70 - latest revision
Canada:
refer to Canadian Electrical Code, CSA
C22.1 Part I - latest revision.If any of the original
internal wiring must be replaced, it must be replaced
with wiring materials having a temperature rating of at
least 105° C and 600 V.
10.1 Line Voltage Thermostat Wiring
10.2 Low Voltage Thermostat with One Burner
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly earthed.
Failure to follow these instructions can result
in death or electrical shock.
Line Voltage
Thermostat
Gnd.
Gnd.
120 V-60 Hz
Supply Circuit
H
N
H
N
Gnd.
L1
L2
T
Low voltage black jumper
wire connected inside all
burners between Purple and
Blue wire; Yellow not used.
Gnd.
120 V-60 Hz
Supply Circuit
H
N
Gnd.
L1
L2
NOTE:
Yellow and Purple wires provide 24 VAC to power thermostat
Low voltage terminal detail:
Thermostat: R to Purple wire;
W to Blue wire; C to Yellow wire
Содержание VANTAGE HEV-100
Страница 2: ......
Страница 4: ......
Страница 24: ...HEV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 20 FIGURE 19 Linear Heater Layout Overview ...
Страница 25: ...SECTION 6 HEATER INSTALLATION 21 FIGURE 20 Linear Heater Layout Overview Continued ...
Страница 40: ...HEV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 36 FIGURE 29 U Tube Heater Layout Overview ...
Страница 41: ...SECTION 7 OPTIONAL HEATER ACCESSORIES 37 FIGURE 30 U Tube Heater Layout Overview Continued ...
Страница 72: ...HEV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 68 ...
Страница 73: ...SECTION12 TROUBLESHOOTING 69 12 2 Manifold Gas Pressure Setting Side View of Heater ...
Страница 78: ......
Страница 79: ...2020 ...
Страница 80: ......