HEV-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
52
8.14 Common Side Wall Horizontal Venting (Category III)
Requirements:
• Maximum of two heaters can be commonly
vented through a side wall.
• Heaters must be of the same BTU output.
• Heaters must be controlled by a common
thermostat.
NOTE:
It is required that all vent pipes and connectors be
fastened together with sheet metal screws and
sealed with high temperature silicone sealant
approved for at least 550 °F (288 °C) (supplied by
others).
The installer must perform a leak test on the
complete venting system. A solution of soap and
water should be used to test the venting system.
Description
Part Number
Vent Terminal 6" (15 cm)
90502101
Note:
A continuous section of type B-vent may only be
used to pass through the outside wall or outside of
the building. Horizontal venting (Category III) does
not allow the use of type B-vent inside of the space.
Содержание VANTAGE HEV-100
Страница 2: ......
Страница 4: ......
Страница 24: ...HEV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 20 FIGURE 19 Linear Heater Layout Overview ...
Страница 25: ...SECTION 6 HEATER INSTALLATION 21 FIGURE 20 Linear Heater Layout Overview Continued ...
Страница 40: ...HEV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 36 FIGURE 29 U Tube Heater Layout Overview ...
Страница 41: ...SECTION 7 OPTIONAL HEATER ACCESSORIES 37 FIGURE 30 U Tube Heater Layout Overview Continued ...
Страница 72: ...HEV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 68 ...
Страница 73: ...SECTION12 TROUBLESHOOTING 69 12 2 Manifold Gas Pressure Setting Side View of Heater ...
Страница 78: ......
Страница 79: ...2020 ...
Страница 80: ......