HEV-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
50
8.11 Horizontal Venting (Category III) 4" (10 cm) Pipe
8.12 Vertical Venting (Category III) 4'' (10 cm) Pipe
NOTE:
It is required that all vent pipes and connectors be fastened together with sheet metal screws and sealed with
high temperature silicone sealant approved for at least 550 °F (288 °C) (supplied by others). The installer
must perform a leak test on the complete venting system. A solution of soap and water should be used to
test the venting system.
Description
Part Number
Vent Terminal (Comb. Wall)
90502100
Vent Terminal
02537801-XX
Description
Part Number
Vent Cap 4" (10 cm)
90502300
Содержание VANTAGE HEV-100
Страница 2: ......
Страница 4: ......
Страница 24: ...HEV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 20 FIGURE 19 Linear Heater Layout Overview ...
Страница 25: ...SECTION 6 HEATER INSTALLATION 21 FIGURE 20 Linear Heater Layout Overview Continued ...
Страница 40: ...HEV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 36 FIGURE 29 U Tube Heater Layout Overview ...
Страница 41: ...SECTION 7 OPTIONAL HEATER ACCESSORIES 37 FIGURE 30 U Tube Heater Layout Overview Continued ...
Страница 72: ...HEV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 68 ...
Страница 73: ...SECTION12 TROUBLESHOOTING 69 12 2 Manifold Gas Pressure Setting Side View of Heater ...
Страница 78: ......
Страница 79: ...2020 ...
Страница 80: ......