EP-300 S
ERIES
P
UMP
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
20 of 31
FIGURE 17: Vertical Ventin
g
9.7 Condensate Tee Assembly
The condensate tee assembly is composed of a tee,
draincap, and condensate trap.
If the system is designed in the condensing mode, then
the installation of a condensate tee assembly is
req
u
ired. The condensate tee assembly, m
u
st be
installed on the inlet side of the p
u
mp assembly if there
is horizontal
v
enting of the p
u
mp,
See Page 21, Figure
18
.
A condensate drain on the discharge side is req
u
ired
if there is
v
ertical
v
enting of the p
u
mp or if there is a
v
ertical rise in the discharge line a
w
ay from the
p
u
mp.
See Page 21, Figure
.
The condensate tee assembly in the discharge line
can be eliminated if the discharge line is horizontal
thro
u
gh the
w
all and pitched do
w
n at least 1/4" per
10' (6 mm per 3 m). This arrangement
w
ill permit
drainage of condensate thro
u
gh the p
u
mp and
o
u
tside
v
ia the horizontal (pitched) discharge line.
20 (51 cm)
Bird Screen
Optional
NOTE:
V
acuum loss
may occur when
using vent caps.
The use of
b
ird screen
to cover vent terminations
is recommended.
Description
Part Number
Tee 6" (15 cm)
01330204
Drain Cap 6" (15 cm)
02718852