SECTION 8: MOTOR WIRING
All
w
iring m
u
st comply
w
ith c
u
rrent
w
iring reg
u
lations
and any local reg
u
lations
w
hich may apply. Al
w
ays
s
w
itch off the s
u
pply and disconnect before ser
v
icing.
8.1 Impeller Rotation Direction
Prior to operation of the p
u
mp in the heating system,
operation and proper rotation of the impeller m
u
st be
v
erified. See impeller rotation direction arro
w
label on
the p
u
mp scroll for the correct rotation direction. For
re
v
erse rotation, follo
w
man
u
fact
u
rer's
w
iring diagram
located on motor.
The motor m
u
st be
w
ired for clock
w
ise or co
u
nterclock-
w
ise rotation as sho
w
n on
w
iring diagram located on
motor.
IMPORTANT: Improper rotation of the impeller
w
ill
not prod
u
ce the
v
ac
uu
m req
u
ired for proper system
operation.
8.2 EP-301 Wirin
g
The EP-301 motor is
w
ired for 1 Ø, 230 V, 60 Hz
operation. For proper motor
w
iring, follo
w
man
u
fac-
t
u
rer's
w
iring diagram located on motor.
When controlled by a CORAYVAC
®
Heating Control,
u
se Contactor Package 28A (P/N 10050012).
See
Page 16, Figure 14
. See ROBERTS GORDON
®
CORAYVAC
®
Heating Control Man
u
al (P/N
10091601NA)
w
iring details.
Wire the press
u
re s
w
itch per the CORAYVAC
®
(P/N 127102NA) for CRV models, CORAYVAC
®
Clas-
sic SF (127302NA) for CRVSF models or VAN-
TAGE
®
CTHN (P/N 152101NA) Installation, Operation
and Ser
v
ice Man
u
als.
Do not directly connect the controller relay terminals to
the p
u
mp motor.
The power to the EP-301 pump is not supplied
by the controller. Power is supplied by a
separate circuit and is switched by the controller
via a contactor with a 120 V AC coil.
See Page 16,
Figure 14
.
FIGURE 14: EP-301 Contactor Wirin
g
Dia
g
ram
8.3 EP-303 Wirin
g
The EP-303 motor can be
w
ired for 3 Ø,
208 V - 230 V/460 V, 60 Hz operation. For proper
motor
w
iring, follo
w
man
u
fact
u
rer's
w
iring diagram
located on motor.
Do not directly connect the controller relay terminals to
the p
u
mp motor.
When controlled by a CORAYVAC
®
Heating Control,
u
se Contactor Package 17A (P/N 10050011).
See
Page 17, Figure 15
. See ROBERTS GORDON
®
CORAYVAC
®
Heating Control Man
u
al (P/N
10091601NA)
w
iring details.
Wire the press
u
re s
w
itch per the appropriate
w
iring dia-
gram in the Controller Installation Man
u
al.
WARNING
Electrical Shock Hazard
Disconnect electrical and gas before
servicing.
This appliance must be connected to a
properly grounded electrical source.
Failure to follow these instructions can result
in death or electrical shock.
Indi
v
id
u
al s
u
pply for p
u
mp
rated for total f
u
ll load c
u
rrent
(
See Page 29, Section 12.5
for
details).