This section describes the components of the sample draw combustible gas detector. The 
sample draw detector consists of the housing, flow system, and detection system.

 

Figure 1:  Sample draw Combustible Gas Detector Component Location

 

Housing

 

The sample draw detector’s fiberglass housing is weather- and corrosion-resistant. It is 
suitable for installation where general purpose equipment is in use.

The housing door is hinged on the left side and is secured by two latches on the right side. 
The flowmeter and status lights are visible through a window in the housing door. 

Four mounting feet are attached to the back of the housing (one at each corner). Use the 
mounting feet to install the housing to a vertical surface. Use the two conduit hubs on the 
bottom of the housing to make wiring connections.

An aluminum subpanel is mounted to the interior of the housing. The sample draw 
detector’s internal components are mounted to the subpanel.

Flow Alarm Se tpo int
Adjustment Po ten tiomet er

Externa l Wiring
Terminal Strip

In le t

Se nso r Wiring
Terminal St rip

Exh aust

Terminal Block

3/4" C on du it
Hub, 2X

Flowmeter

Particle filter

Byp ass valve

LE L Transmitter

Pu mp /flo w sw itch
termina l block

Flow Adjust
Potentiometer

Fail LE D

Pilot LE D

TP 

+

TP

ZERO

SPAN

GND

24V

4-20

RED

WHT

GRN

BLK

POWER/SIG

SENSOR

P/N 57-1050RK

REV. 0

Factory Se t Pots

LEL 
sensor

Zero Pot

Span Pot

JUMPER PI NS FOR 
FACTORY U SE ONLY

Test Po ints
10 0 - 500 mV range

Mounting
Foot, 4X

Содержание 35-3000RKA-LEL

Страница 1: ...detector Table 1 Specifications Target Gas Combustible Gas Input Power 24 VDC Construction housing Fiberglass polyester NEMA 4X Dimensions 8 5 in H x 6 5 in W x 4 25 in D Weight 4 5 lbs Sampling Meth...

Страница 2: ...re attached to the back of the housing one at each corner Use the mounting feet to install the housing to a vertical surface Use the two conduit hubs on the bottom of the housing to make wiring connec...

Страница 3: ...d or clogged Pump The pump is behind the main circuit board near the top of the sample draw detector The pump pulls the gas sample into the sample draw detector The pump operates on 24 VAC which is ge...

Страница 4: ...he EXHAUST fitting accepts 1 4 in rigid tubing See the Installation section on page 7 to connect tubing to the EXHAUST fitting Detection System The detection system consists of the combustible gas sen...

Страница 5: ...f the transmitter The transmitter is factory wired to the sensor and main circuit board Test points The test points are located on the left side of the transmitter and are labeled TP and TP A 100 mV 5...

Страница 6: ...sure switch are factory wired to the circuit board See the Installation on page 7 for all wiring procedures related to the sample draw detector Relay The relay is to the left of the detector terminal...

Страница 7: ...ider the following when you select the mounting site Is there enough room to open the housing door and make wiring connections at the bottom of the housing and tubing connections at the right of the h...

Страница 8: ...to seal the connection between the tubing and the INLET fitting See Appendix A Parts List for an example of an appropriate metal insert 2 Place the opposite end of the tubing at the sampling area CAUT...

Страница 9: ...e Gas Detector 4 20 Feedback Ground WHT GR N BLK GN D 2 4 V _ LEL O2 AM P P AM P 4 2 0 GREEN BLA C K WH ITE RED PUMP ASSY INTERNALLY WIRED 24VDC GND 24V 4 20 RD PUM P PSW TP TP ZERO SPAN GND 24V 4 20...

Страница 10: ...of the sample line with your thumb If the flowmeter ball drops to the bottom of the flowmeter the incoming sample line is not leaking 7 Remove your thumb from the sample line verify the flowmeter retu...

Страница 11: ...e target gas Preparing for the response test NOTE This procedure describes the RKI calibration kit that includes a gas collection bag A calibration kit that uses a demand flow regulator is also availa...

Страница 12: ...ems you may encounter with the sample draw combustible gas detector NOTE This troubleshooting guide describes sample draw detector problems only See the instruction manual for monitoring device if it...

Страница 13: ...pump etc The sample draw detector is malfunctioning The demand flow regulator is not operating properly if one is used for calibration instead of a gas bag Recommended action 1 Verify that the calibra...

Страница 14: ...row indicates the direction of the sample flow 3 Disconnect the filter from the elbows on each end of the filter then remove the filter from the sample draw detector 4 Make sure the arrow is pointing...

Страница 15: ...low to 0 6 SCFH 2 Slowly turn the low flow potentiometer counterclockwise just until the sample draw detector goes into low flow alarm NOTE The low flow potentiometer is accessible through a circular...

Страница 16: ...the correct test points output for the calibrating sample Output mV calibrating sample fullscale X 400 100 For example with a calibrating sample of 50 LEL and a fullscale setting of 100 LEL the corre...

Страница 17: ...e sample tubing from the inlet line then close the clamp Setting the Response Reading 1 Connect the sample tubing from the gas collection bag to the fixed flow regulator then open the clamp 2 Screw th...

Страница 18: ...Filter Boston DFU9933 05 DQ 57 1050RK Transmitter specify target gas when ordering 61 0145RK Combustible gas sensor NC 6240 plug in type LEL range 81 0002RK 01 Calibration cylinder 50 LEL Hydrogen 34...