T3A Transmitter • 33
NOTE:
For maximum safety, the fault terminal MUST be used. A fail-safe relay will NOT
notify the user of all potential device failures. The fail-safe setting should ONLY be
enabled to provide enhanced safety protection when the fault terminal CANNOT be
used.
The factory default settings on the T3A for Relay 1 and Relay 2 fail-safe are No (Off).
If the fault terminal cannot be used, RKI Instruments recommends one of the following
configurations:
Relay 1: Fail-Safe Setting
1. If necessary, enter the Product Settings and Configuration menu by pressing and holding
the MENU button for 6 seconds.
2. Press and release the MENU button until the Relay 1 Failsafe screen appears.
3. Use the ADD and SUB buttons to select the desired fail-safe setting for Relay 1. Select
“Yes” to turn the fail-safe setting on, or select “No” to leave the fail-safe setting off.
4. Press the MENU button to select the desired setting and to advance to the Relay 2 fail-safe
setting screen.
Recommended Configurations for Relay Fail-Safe Setting
Power Source
Relay Wiring
Fail-Safe
Outcome
T3A
Normally-Closed (NC) No (Off)
Normal Operation: Closed
Alarm Activation: Open
T3A
Normally-Open (NO)
Yes (On)
Normal Operation: Closed
Alarm Activation: Open
External Power Supply Normally-Closed (NC) Yes (On)
Normal Operation: Open
Alarm Activation: Closed
External Power Supply Normally-Open (NO)
Yes (On)
Normal Operation: Closed
Alarm Activation: Closed