18
•
Installation
35-3010RKA-04H Sample-Draw Detector Head
6. Close and latch the housing door of the sample-draw detector.
CAUTION:
Leave the cable shield drain wire insulated and disconnected at the
sample-draw detector. You will connect the opposite end of the drain
wire at the controller.
7. Route the cable or wires in conduit leading from the sample-draw detector to the controller.
8. Connect the drain wire to an available chassis ground at the controller. RKI controllers
typically have a ground stud that can be used to ground the cable’s drain wire.
Figure 7: External (Field) Wiring, Sample-Draw Detector
LEL
(Controller Transmitter
Terminals)
24 VDC
4/20 (Feedback)
+
Interconnect Terminal Strip
Oxygen
(Controller Trasnmitter
Terminals)
+
24 VDC
4/20 (Feedback)
Reset Switch
Sample Draw Housing
Main Circuit Board