35-3010RKA-04H Sample-Draw Detector Head
Description
•
15
Sensor/Transmitter Terminal Strip
The sensor/transmitter terminal strip is the sixteen-point terminal strip near the right edge of the
circuit board. Use the transmitter terminal strip to connect sensors or transmitters to the main
circuit board.
NOTE:
The sensors and transmitters are factory wired to the sensor/transmitter terminal strip.
See “Wiring the Sample-Draw Detector” on page 17 for all wiring procedures related to
the sample-draw detector.
Amp 1 and Amp 2 Circuits
These circuits are located to the left of the sensor/transmitter terminal strip. They each include test
points, a zero pot, and a span pot. Amp 1 is on the left and is for the CO channel. Amp 2 is on the
right and is for the H2S channel.
The zero and span pots are used during calibration. Use the span pot to make adjustments to gas
response readings and the zero pot to make adjustments to the zero reading.
The test points are labeled
CAL-1
and
CAL+1
for the CO channel and
CAL-2
and
CAL+2
for
the H2S channel. No output is available at either set of test points.
Pump Terminal Strip
The pump terminal strip is the four-point terminal in the top left corner of the circuit board. Use
the pump terminal strip to connect the pump and pressure switch to the main circuit board.
NOTE:
The pump and pressure switch are factory-wired to the circuit board. See “Wiring the
Sample-Draw Detector” on page 17 for all wiring procedures related to the sample-draw
detector.
Relay
The relay is approximately in the middle of the circuit board. The relay is a four pole, double-
throw (4PDT) relay and is rated for 2 amps at 25 VDC (resistive). If the pressure switch senses a
low flow condition, the relay interrupts the sensor signal from the direct connect hydrogen and
oxygen channels and the 4-20 mA signal from the CO and H
2
S channels which will cause a
downscale reading at the controller or recording device.
NOTE:
There is no flow fail indication for the hydrogen and oxygen channels on the
35-3010RKA-04H Sample Draw Adapter.
Reset Switch
A small reset button is located in the upper left corner of the main PCB. When a low flow
condition occurs, the pump will be shut off. To reset the low flow condition and start the pump
again, press and hold the reset switch for about 2 seconds, then release.