9. SPECIFICATIONS
Number of phase:
Single-phase
Maximum load current:
20 A AC, 30 A AC, 45 A AC, 60 A AC, 80 A AC and 100 A AC
For the temperature characteristic of maximum load current, see temperature characteristic graph of
load current. (P. 3)
Minimum load current:
0.6 A (20 A type), 1 A (30 A, 45 A, 60 A, 80 A and 100 A types)
Power supply voltage:
90 to 264 V AC [Including power supply voltage variation] (Rating: 100 to 240 V AC)
Power frequency:
50/60 Hz (Automatic discriminating)
Allowable power frequency variations:
±
1 Hz (Performance guarantee)
±
2 Hz (Operation guarantee)
Input signal:
Current input 4 to 20 mA DC (Input impedance: 100
Ω
)
Voltage input 0 to 10 V DC
(Input impedance: 68 k
Ω
)
Voltage input 1 to 5 V DC
(Input impedance: 30 k
Ω
)
Voltage pulse input 0/12 V DC (Input impedance: 30 k
Ω
)
Dry contact input
(Input impedance: 47 k
Ω
)
Output voltage range:
0 to 98 % of rating voltage
Applicable load:
Phase control:
Linearity (R: resistor) load
Control of primary side of a transformer (magnetic field density 1.25 T or less)
Zero-cross control: Linearity (R: resistor) load
Control method:
Phase control
(No feedback)
Zero-cross control (No feedback)
Output setting range:
Internal manual set value:
0.0 to 99.9 %
(Set by theTHV-1 front keys)
External manual set value:
0 to 100 %
(Set by the setter
1
)
External gradient set value:
0 to 100 %
(Set by the setter
1
)
Internal gradient set value:
0 to 100 % (0.00 to 1.00) (Set by the THV-1 front keys)
Output limiter (high) set value: 0.0 to 99.9 %
(Set by the THV-1 front keys)
Output limiter (low) set value: 0.0 to 99.9 %
(Set by the THV-1 front keys)
Base-up set value:
0.0 to 99.9 %
(Set by the THV-1 front keys)
1
Option
Output mode:
Proportional phase angle to input
2
Proportional voltage to input
2
Proportional square voltage (electric power) to input
2
Constant current control (option)
2
2
When the phase control use the linearity (R: resistor) load
Ramp (Soft-start/Soft-down) function:
Setting range: 0.0 to 99.9 seconds (Set by the THV-1 front keys)
Auto/Manual mode selection:
External dry contact
External contact closed: Manual mode
External contact open: Auto mode
Heater break alarm function (option):
When the power source ripples of main circuit is sine-wave
Input:
Current transformer (built-in)
Measured accuracy: Within
±
2 A (20 A and 30 A types)
Within
±
10 % of maximum load current (45 A, 60 A, 80 A and 100 A types)
Output:
1 point, open collector output 24 V DC, Max. 100 mA
Output ON/OFF at alarm is selectable.
Current limiter function (option):
Setting range
20 A, 30 A: 0.0 to 32.0 A
45 A: 0 to 55 A
60 A: 0 to 70 A
80 A: 0 to 90 A
100 A: 0 to 110 A
If a current limit value is set to its maximum value, the current limit function is deactivated.
Cooling method:
Natural
convection
Ambient temperature:
0 to 40
°
C (Performance guarantee range),
−
15 to +55
°
C (Operation guarantee range)
Ambient humidity:
5 to 95 % RH (Non-condensing)
Withstand voltage:
Between main circuit, power terminals and radiation fins: 1 minute at 2000 V AC
Insulation resistance:
Between main circuit, power terminals and radiation fins: 20 M
Ω
or more at 500 V DC
Mounting method:
Vertical
mounting
Dimensions:
See 4.2 Dimensions (P. 4).
Weight:
Approx. 0.9 kg (20 A and 30 A types)
Approx. 1.3 kg (45 A and 60 A types)
Approx. 1.9 kg (80 A and 100 A types)