RKC INSTRUMENT THV-1 Скачать руководство пользователя страница 14

IMR01M01-E5

 

14 

7. FUNCTIONS 

7.1 Selecting Manual Mode Type and Input Signal Monitor 1 

Displays one of the following values depending on the control mode and the setting of Contact Input Action Selection. 

 

• 

Input signal from controller 

• 

External manual set value (Input signal from external manual setter) 

• 

Internal manual set value 

, input signal from controller is always displayed on Input Signal Monitor 1 when the contact input function is not used. 

 

(The displayed item on Input Signal Monitor 1) 

Contact input 

State of external contact 

action selection 

Contact closed 

(Manual mode) 

Contact open 

(Auto mode) 

0: External manual mode 

 Auto mode 

External manual set value 

Input signal from controller 

1: Internal manual mode 

 Auto mode 

Internal manual set value 

Input signal from controller 

2: Internal manual mode 

(fixed) 

Internal manual set value 

 

 

 

Select manual mode type 

Example: Select manual mode with internal manual set value. 

1. 

Go to the parameter “Contact Input Action” in Parameter Group 1. 
Set it to “1: Internal manual mode 

 Auto mode.” 

 

2. 

The input signal from controller is displayed when the contact is open. 
The internal manual set value is displayed when the contact is closed. 

 

7.2 Control Method 

 

Phase control 

Phase control is to continuously control electric power supplied to a load by 
changing phase angle 

θ

 of AC

 

voltage applied to the load. Each half-cycle has 

ON and OFF time. 

 

 

 

 

 

 

Zero-cross control (Continuous) 

Continuous Zero-cross control is to control electric power supplied to a load by 
turning the power supply voltage ON and OFF at the point of 0 V AC so that 
the high frequency noise can be suppressed compared with phase control. 
This on and off time is typically measured in milliseconds. 

 
 

 

50 % 

 

 

 

 

Zero-cross control (Input synchronous type) 

Input Synchronous type Zero-cross control is to turn the power supply ON and 
OFF synchronously with the pulse signal from a controller. 
This on and off time is typically measured in seconds. 

Input 

signal 

OFF OFF 

ON 

 

 

7.3 Ramp Function (Soft-Start/Soft-Down Function) 

Soft-start/soft-down function gradually ramps up/down the output voltage to the demand level over the set time to prevent a 
sudden change in load or voltage. 
The soft-start/soft-down time sets a period of time from 0 to 100 % or 0 to 100 %. 

 

 

100%

Output voltage  Soft-start time 

 Time 

 Time 

Input signal 

and setting 

Soft-down time 

100% 

Output voltage 

 Time 

 Time 

80% 

Output limiter (high limit) 

0%

0%

Soft-start time 

Soft-down time 

Input signal 

and setting 

 

Soft-start/Soft-down action diagram 

 

If a load generating large rush current is used, thyristor break-down may occur when no soft-start time is 
appropriately set. 

 

In zero-cross control, no rush current can be suppressed even if the soft-start time is set. 

Contact input action 
selection 

Contact input 
closed 
(Manual mode) 

THV-1 

 
 

Содержание THV-1

Страница 1: ...wer is turned on to prevent electric shock instrument failure or incorrect action To prevent instrument damage or failure protect the power line and the input output lines with a protection device suc...

Страница 2: ...meter knob and scale plate 2 sets and Connector plug 3 Fuse unit for 20 A and 30 A fast blow fuse 1 piece and holder 3 circuits type 4 Output voltmeter 150 V span For phase control 5 Output voltmeter...

Страница 3: ...temperature exceeds 40 C 0 20 40 60 80 100 10 20 30 40 50 55 Load current Temperature characteristic of load current 60 0 20 40 60 80 100 10 20 30 40 50 55 20 A 30 A 45 A 80 A and 100 A types Includin...

Страница 4: ...ng dimensions Dimensions 147 5 a a Dimensions when the connector plug optional is connected When connecting the connector plug install the thyristor by taking enough space for its wiring into account...

Страница 5: ...t does not build up This unit generates heat It is cooled by air convection when installed as shown Failure to observe the instructions in 4 2 and 4 3 could cause damage to the instrument equipment or...

Страница 6: ...d power supply terminal Main circuit terminals L2 1 2 3 4 5 Power supply 100 to 240 V AC 50 60 Hz V Output voltmeter option Can use it only in phase control THV 1 Main circuit terminals L1 Load Instru...

Страница 7: ...type change However for a voltage input of 1 to 10 V DC no input signal can be changed 5 3 Wiring for connector The connector is used for contact input auto manual mode selection external gradient se...

Страница 8: ...r Pin number External contact Pin number Pin number For input signal wiring see Current input 4 to 20 mA DC voltage input 0 to 10 V DC 1 to 5 V DC and voltage pulse input 0 12 V DC P 6 Auto Manual mod...

Страница 9: ...nt set value monitor External manual set value monitor Contact input state monitor Press the key for 2 sec Error or alarm display If any error or alarm occurs the present display is changed to the err...

Страница 10: ...Soft start time Control method Setting range Control method 0 Phase control 1 Zero cross control When the value is changed it will be automatically stored after three seconds without any key operatio...

Страница 11: ...1 Display of the Input Signal Monitor 1 Contact input action Contact open Contact close 0 Input signal from controller External Manual Set value 1 Input signal from controller Internal Manual Set val...

Страница 12: ...for heater break alarm Type 2 When the control method is Zero cross Control RKC recommends Set the heater break alarm set value to approximately 80 of the reading of current transformer input Set the...

Страница 13: ...roller External gradient set value monitor 0 to 100 Display the external gradient set value External manual set value monitor 0 to 100 Display the external manual set value Contact input state monitor...

Страница 14: ...hanging phase angle of AC voltage applied to the load Each half cycle has ON and OFF time Zero cross control Continuous Continuous Zero cross control is to control electric power supplied to a load by...

Страница 15: ...the minimum output will not go below the output limiter low Output limiter high has priority to the output value 2 calculated with Gradient Setting and Base Up setting function The maximum output fro...

Страница 16: ...using constant current control function If there is a difference between the maximum load currents flowing through the thyristor and the heater compensate for the difference by setting the gradient If...

Страница 17: ...set value The alarm can be output when a heater break occurs by setting the heater break alarm set value Heater break alarm 2 set value This alarm set value can be used as an auxiliary alarm For exam...

Страница 18: ...break alarm set value for the preset number of consecutive sampling cycles an alarm status is produced When heater current can not be turned off Thyristor break down or permanent damage When the phas...

Страница 19: ...produced When heater current can not be turned off Thyristor break down or permanent damage When the control output is OFF and the current transformer input value is equal to or greater than the heat...

Страница 20: ...nction This is the function of limiting a measured current value to a value not exceeding the preset current limit value A current value is measured for each constant cycle and then the maximum phase...

Страница 21: ...ower once If an error occurs after the power is turned on again please contact RKC sales office or the agent 32 Power frequency error 2 Thyristor output OFF Check the value of power supply frequency a...

Страница 22: ...low set value 0 0 to 99 9 Set by the THV 1 front keys Base up set value 0 0 to 99 9 Set by the THV 1 front keys 1 Option Output mode Proportional phase angle to input 2 Proportional voltage to input 2...

Страница 23: ...ate align the arrow on the knob with 0 on the scale plate 0 10 2 Output voltmeter 150 V span or 300 V span V 14 29 5 10 80 35 67 48 Unit mm 64 2 M3 16 52 2 M4 32 32 18 5 29 5 54 0 5 0 Panel cutout dim...

Страница 24: ...MENT INC HEADQUARTERS 16 6 KUGAHARA 5 CHOME OHTA KU TOKYO 146 8515 JAPAN PHONE 03 3751 9799 81 3 3751 9799 E mail info rkcinst co jp FAX 03 3751 8585 81 3 3751 8585 The first edition JUN 2002 IMQ00 Th...

Отзывы: