RKC INSTRUMENT THV-1 Скачать руководство пользователя страница 11

 

IMR01M01-E5

 

11 

Continued from the previous page. 

Parameter group 1 

Name 

Parameter 

symbol 

Setting range 

Factory 

set 

value 

Details 

Reference 

page 

Soft-start time

 1

 

 

 

0.0 to 99.9 seconds 

0.1 

Set the soft-start time. 

P. 14 

Soft-down time 

 

 

0.0 to 99.9 seconds 

0.1 

Set the soft-down time. 

P. 14 

Internal gradient 
set value 

 

 

0.00 to 1.00 
0.00: Internal gradient 

0 % 

1.00: Internal gradient 

100 % 

1.00 

Set the internal gradient set value. 

P. 15 

Output limiter 
(high) 

 

 

0.0 to 99.9 % 

99.9 

Set the output limiter (high) setting.

 2

 

P. 15 

Output limiter 
(low) 

3

 

 

 

0.0 to 99.9 % 

0.0 

Set the output limiter (low).

 2 

The base-up set value is effective only 
when the output limiter (low) is set to 
0.0. 

P. 15 

Base-up 
set value 

3

 

 

 

0.0 to 99.9 % 

0.0 

Set the base-up set value (output 
bias) of output.

  4

 The base-up set 

value is effective only when the output 
limiter (low) is set to 0.0. 

P. 15 

Output mode for 
phase control

 5

 

 

 

0: Proportional phase 

angle to input 

1: Proportional voltage 

to input 

2: Proportional square 

voltage (electric 
power) to input 

3: Constant current 

control

 6

 

Select the output method for phase 
control with linearity (R: resistor) load. 
The setting is invalid when zero-cross 
control is selected. 

P. 16 

Internal manual 
set value 

 

 

0.0 to 99.9 % 

0.0 

Set the internal manual set value. 

 

Contact input 
action 

 

 

0: External manual 

mode 

 Auto mode 

1: Internal manual mode 

 Auto mode 

2: Internal manual mode   

(fixed) 

Select the contact input action. This 
selection also affects the display of the 
Input Signal Monitor 1. 

Display of the Input Signal Monitor 1 

Contact 

input action 

Contact 

open 

Contact 

close 

0 Input 

signal 

from 
controller 

External 
Manual Set 
value 

1 Input 

signal 

from 
controller 

Internal 
Manual Set 
value 

Internal Manual Set value 

(See P. 10) 

See 7.1 on 

page 14. 

Maximum load 
current set value 
for alarm 

7

 

 

 

0.0 to 32.0 A 

(20 A/30 A) 

0 to 55 A

 

(45 A) 

0 to 70 A

 

(60 A) 

0 to 90 A

 

(80 A) 

0 to 110 A

 

(100 A)

 

30.0 

Sets the maximum load current value 
at an output of 100 %. The value is 
used for the heater break alarm 1 and 
heater break alarm 2. 

P. 17 

If a load generating large rush current is used, thyristor break-down may occur when no soft-start time is appropriately set. 

Also in zero-cross control, no rush current can be suppressed even if the soft-start time is set.

 

Output Limiter (High) value must be equal or higher than Output Limiter (Low). 

These function can not be used together. 

The output value will not exceed the Output Limiter (High). 

The output mode setting is invalid when the control method is zero-cross control. 

These parameters cannot be set when the heater break alarm, current limiter and constant current control functions are 
not provided. If there is a difference between the maximum load currents flowing through the thyristor and the heater 
with constant current control selected, compensate for the difference by setting the gradient. Set the gradient so that the 
maximum heater load current will flow through the heater at an input signal of 100% from the controller. (See P. 16) 

These parameters are not displayed when the heater break alarm, current limiter and constant current control functions 
are not provided. 

Continued on the next page. 

Содержание THV-1

Страница 1: ...wer is turned on to prevent electric shock instrument failure or incorrect action To prevent instrument damage or failure protect the power line and the input output lines with a protection device suc...

Страница 2: ...meter knob and scale plate 2 sets and Connector plug 3 Fuse unit for 20 A and 30 A fast blow fuse 1 piece and holder 3 circuits type 4 Output voltmeter 150 V span For phase control 5 Output voltmeter...

Страница 3: ...temperature exceeds 40 C 0 20 40 60 80 100 10 20 30 40 50 55 Load current Temperature characteristic of load current 60 0 20 40 60 80 100 10 20 30 40 50 55 20 A 30 A 45 A 80 A and 100 A types Includin...

Страница 4: ...ng dimensions Dimensions 147 5 a a Dimensions when the connector plug optional is connected When connecting the connector plug install the thyristor by taking enough space for its wiring into account...

Страница 5: ...t does not build up This unit generates heat It is cooled by air convection when installed as shown Failure to observe the instructions in 4 2 and 4 3 could cause damage to the instrument equipment or...

Страница 6: ...d power supply terminal Main circuit terminals L2 1 2 3 4 5 Power supply 100 to 240 V AC 50 60 Hz V Output voltmeter option Can use it only in phase control THV 1 Main circuit terminals L1 Load Instru...

Страница 7: ...type change However for a voltage input of 1 to 10 V DC no input signal can be changed 5 3 Wiring for connector The connector is used for contact input auto manual mode selection external gradient se...

Страница 8: ...r Pin number External contact Pin number Pin number For input signal wiring see Current input 4 to 20 mA DC voltage input 0 to 10 V DC 1 to 5 V DC and voltage pulse input 0 12 V DC P 6 Auto Manual mod...

Страница 9: ...nt set value monitor External manual set value monitor Contact input state monitor Press the key for 2 sec Error or alarm display If any error or alarm occurs the present display is changed to the err...

Страница 10: ...Soft start time Control method Setting range Control method 0 Phase control 1 Zero cross control When the value is changed it will be automatically stored after three seconds without any key operatio...

Страница 11: ...1 Display of the Input Signal Monitor 1 Contact input action Contact open Contact close 0 Input signal from controller External Manual Set value 1 Input signal from controller Internal Manual Set val...

Страница 12: ...for heater break alarm Type 2 When the control method is Zero cross Control RKC recommends Set the heater break alarm set value to approximately 80 of the reading of current transformer input Set the...

Страница 13: ...roller External gradient set value monitor 0 to 100 Display the external gradient set value External manual set value monitor 0 to 100 Display the external manual set value Contact input state monitor...

Страница 14: ...hanging phase angle of AC voltage applied to the load Each half cycle has ON and OFF time Zero cross control Continuous Continuous Zero cross control is to control electric power supplied to a load by...

Страница 15: ...the minimum output will not go below the output limiter low Output limiter high has priority to the output value 2 calculated with Gradient Setting and Base Up setting function The maximum output fro...

Страница 16: ...using constant current control function If there is a difference between the maximum load currents flowing through the thyristor and the heater compensate for the difference by setting the gradient If...

Страница 17: ...set value The alarm can be output when a heater break occurs by setting the heater break alarm set value Heater break alarm 2 set value This alarm set value can be used as an auxiliary alarm For exam...

Страница 18: ...break alarm set value for the preset number of consecutive sampling cycles an alarm status is produced When heater current can not be turned off Thyristor break down or permanent damage When the phas...

Страница 19: ...produced When heater current can not be turned off Thyristor break down or permanent damage When the control output is OFF and the current transformer input value is equal to or greater than the heat...

Страница 20: ...nction This is the function of limiting a measured current value to a value not exceeding the preset current limit value A current value is measured for each constant cycle and then the maximum phase...

Страница 21: ...ower once If an error occurs after the power is turned on again please contact RKC sales office or the agent 32 Power frequency error 2 Thyristor output OFF Check the value of power supply frequency a...

Страница 22: ...low set value 0 0 to 99 9 Set by the THV 1 front keys Base up set value 0 0 to 99 9 Set by the THV 1 front keys 1 Option Output mode Proportional phase angle to input 2 Proportional voltage to input 2...

Страница 23: ...ate align the arrow on the knob with 0 on the scale plate 0 10 2 Output voltmeter 150 V span or 300 V span V 14 29 5 10 80 35 67 48 Unit mm 64 2 M3 16 52 2 M4 32 32 18 5 29 5 54 0 5 0 Panel cutout dim...

Страница 24: ...MENT INC HEADQUARTERS 16 6 KUGAHARA 5 CHOME OHTA KU TOKYO 146 8515 JAPAN PHONE 03 3751 9799 81 3 3751 9799 E mail info rkcinst co jp FAX 03 3751 8585 81 3 3751 8585 The first edition JUN 2002 IMQ00 Th...

Отзывы: