5. COMMUNICATION IDENTIFIERS
IMSRM04-E8
57
Identifier EI: Operation mode transfer
Changes each channel operation mode of TIO module.
[Data range]
0: Unused mode
If set to "Unused," no control, monitor or alarm monitor is performed. Use this when replacing the
module, or during equipment maintenance and inspection.
1: Monitor mode
If set to "Monitor," only the operation relating to monitor is performed. (capture of measured value
(PV)). No control or alarm monitor is performed. Use this when equipment operation is temporarily
stopped.
2: Alarm mode
If set to "Alarm," monitor or alarm monitor is performed, but no normal mode to perform control,
monitor or alarm monitor. No control is performed. Use this mode when stopping equipment
operation temporarily.
3: Normal mode
Selected to normal mode to perform control, monitor or alarm monitor.
Polling example:
E
O
T
E I
E
N
Q
A
C
K
S
T
X
E I
0 1
3 ,
0 2
...
E
T
X
B
C
C
* Omit the operation panel address when the connection is made directly to control unit.
Selecting example:
E
O
T
S
T
X
E I
0 1
3 ,
0 2
...
E
T
X
B
C
C
E
O
T
A
C
K
* Omit the operation panel address when the connection is made directly to control unit.
Even if the temperature rise completion function is set to the Unused mode, it will continue
to be effective. If the temperature rise completion function is also to be made invalid,
change the setting of the temperature rise completion trigger function to "No."
Identifier
Comma
Space
Data
(1 digit)
Next to identifier
Channel
No.
Channel
No.
Channel
No.
Channel
No.
Identifier
Identifier
Operation
panel
address
*
Operation
panel
address
*
Unit
address
Unit
address
Data
(1 digit)
Comma
Space
Host computer send
Host computer send
Host computer send
Host computer send
SR Mini SYSTEM send
SR Mini SYSTEM send