5. COMMUNICATION IDENTIFIERS
IMSRM04-E8
46
Identifier HE: Temperature rise completion condition
Identifier HD: Temperature rise completion range
Identifier HS: Temperature rise completion trigger
Identifier T3: Temperature rise completion soak time
Identifier used for each setting related to the presence or absence of the temperature rise completion
trigger function.
HE: Temperature rise completion condition (Read only)
Data range: 0: Rise not complete
1: Rise completed
HD: Temperature rise completion range (Read and write)
Data range: 1 to 10
°
C or 1 to 20
°
F
HS: Temperature rise completion trigger (Read and write)
Data range: 0: Unused
1: Used
T3: Temperature rise completion soak time (Read and write)
Data range: 0 to 360 min.
Temperature rise completion condition, temperature rise completion trigger
and temperature rise completion range
Used when a temperature rise is assumed to be completed when the temperature set value (PV) is
within the width set on both sides from the temperature set value (SV).
The width from the temperature set value at this time becomes the temperature rise completion range,
and thus the temperature rise completion condition can be checked by the output. "Used/Unused" of
the temperature rise completion function can be selected depending on whether the temperature rise
completion trigger.
If the function is set to two or more channels, the temperature rise is completed when the temperature
rise in all the channels in which this function is set has been completed. In addition, even when the
measured temperature is finally within the temperature rise completion range as a result of a
temperature drop, if the measured temperature is first higher than the set temperature, this is
determined to be in the temperature rise completion condition.
PV2
PV1
−
+
Temperature rise
completion range
Temperature rise completion trigger point
(Rise completion)
Temperature
set value (SV)